2013-03-04 11:47:53FAILED STATUS:
  
 #1 DOMESTIC WATER TIE-IN LOCATION IS SHOWN INCORRECTLY.
 WE HAVE NO KNOWLEDGE OF A CITY WATERMAIN EXISTING OFF
 PALM BEACH LAKES BLVD.
  
 #2 DOMESTIC SERVICE IS AVAILABLE FROM AUSTRAILIAN AVE
 THRU AN EASEMENT, CONTACT ENGINEERING SERVICES
 DEPARTMENT, BRIAN MOREE (561) 494-1098 FOR A
 COORDINATION MEETING. DOMESTIC WATER METER AND SEWER
 CLEAN-OUT WILL BE REQUIRED TO BE AT PROPERTY LINE JUST
 INSIDE THE PROPERTY IN AN EASEMENT.
 CLOSEST LOCATION OF WATER AND SEWER STUBS AREA AT
 SOUTH-WEST CORNER OF LOT.
  
 #3 SANITARY SEWER SERVICE IS NOT SHOWN FOR PROPOSED ICE
 HOUSE.
  
 #4 CONSTRUCTION WILL TRIGGER THE MAIN BUILDING TO TIE
 CORRECTLY INTO A CITY OF WPB WATER MAIN.
  
 THANK YOUR FOR YOUR ATTENTION:
  