| 2013-02-23 12:26:42 | 6801 (6610) NORTH JOG ROAD | | | PERMIT #13020494 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE PERMIT APPLICATION ADDRESS DOES NOT MATCH THE | | | CORRECT ADDRESS INDICATED ON THE PLANS. | | | | | | PROVIDE A RISER DETAIL(S). | | | | | | FIRE DEPARTMENT CONNECTION SHALL BE LOCATED WITHIN 150 | | | FEET OF A FIRE HYDRANT. | | | | | | PLANS DO NOT INDICATE WHAT PIPING MATERIAL WILL BE USED | | | FOR THE UNDERGROUND INSTALLATION. | | | | | | PLANS DO NOT INDICATE THE PIPING MATERIAL OF THE | | | EXISTING 4" WATER MAIN. | | | | | | THE PLANS ARE NOT CLEAR HOW THE PIPING IS BEING ROUTED | | | FROM THE "SUB CONTRACTOR" TRAILER TO THE "MATERIAL | | | RECEIVING" TRAILER. | | | | | | SUBMIT PRODUCT DATA FOR THE CPVC PIPING AND BACKFLOW | | | PREVENTER TO BE INSTALLED. PROVIDE DOCUMENTATION | | | SUPPORTING THE USE OF EXPOSED CPVC PIPING. | | | | | | FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED | | | SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. | | | | | | PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE | | | DEPARTMENT CONNECTION. | | | | | | IN ADDITION TO TAMPER SWITCHES, PROVIDE CHAIN WITH LOCK | | | FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN | | | POSITION. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|