2013-02-22 08:50:062010 FBC
  
 DENIED BY ELECTRIC
  
 1) SUBMIT TWO SETS OF ELECTRIC RISER DIAGRAMS WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL, COMPLETE
 LOAD CALCULATIONS AND PANEL SCHEDULES. CITY AMENDMENTS
 107.3.5.3
  
 2) SUBMIT TWO SETS OF ELECTRICAL FLOOR PLANS SHOWING
 THE LOCATIONS OF ALL NEW AND EXISTING METERS, PANELS,
 RECEPTACLES AND OUTLETS. 2008 NEC 210.50 AND 210.70
  
 3) SHOW COMPLIANCE WITH NEC 210.12 FOR REQUIRED AFCI ,
 NEC 210.8 FOR GFCI AND NEC 406.11 FOR TAMPER RESISTANT
 RECEPTACLES.
  
 4) SHOW COMPLIANCE WITH FBC R314.3.1 FOR REQUIRED SMOKE
 ALARMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714