| Plan Review Notes For Permit 13020365 |
| Permit Number |
13020365 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-14 17:40:29 | RESIDENTIAL (R3) ROOFING BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE PRODUCT APPROVALS AS REQUIRED BY DCA RULE | | | 9N-3 FOR: | | | A) ROOF TILE ADHESIVE. SEE CONCRETE TILE NOA FOR LISTED | | | ADHESIVES. | | | | | | B) ROOF UNDERLAYMENT AS SPECIFIED ON SHEET A2.2. SEE | | | ARCHITECTURAL PLANS. | | | | | | 2- FLAT ROOF NOA 09-0224.01 SUBMITTED: PROVIDE SIGNED | | | AND SEALED RAS 117 CALCULATIONS. AS REQUIRED BY GENERAL | | | LIMITATION #7 TO RESIST THE LOADS REQUIRED BY SEC. | | | R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. | | | | | | ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 | | | CALCULATIONS TO TAKE INTO CONSIDERATION THE EXPOSURE | | | AND DESIGN PRESSURES CALCULATED BY THE ENGINEER OF | | | RECORD ON SHEET S3.0 OF THE HOUSE APPROVED PLANS. | | | | | | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. OF CITY | | | AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|