Plan Review Notes
Plan Review Notes For Permit 13020330
Permit Number 13020330
Review Stop P
Sequence Number 1
Notes
Date Text
2013-03-19 11:29:01RESIDENTIAL (R3) ALTERATION PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROPOSED LOCATION OF NEW WATER HEATER IS NOT
 ALLOWED. SEC. P2801.3 OF 2010 FBC-RESIDENTIAL. PROPOSED
 LOCATION DOESN'T ALLOW FOR INSPECTION SERVICE, REPAIR
 AND REPLACEMENT. SEE SEC. M1305. REVISE PLANS AS
 REQUIRED.
  
 2- REVISE PLUMBING RISER DIAGRAM. EACH WET-VENTED
 FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE
 HORIZONTAL WET VENT AS REQUIRED BY SEC. P3108.1 OF 2010
 FBC-RESIDENTIAL. BATHROOM TUB DRAIN NEEDS TO CONNECT
 DIRECTLY TO THE HORIZONTAL WET VENT.
  