| Plan Review Notes For Permit 13020330 |
| Permit Number |
13020330 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-03-19 11:29:01 | RESIDENTIAL (R3) ALTERATION PLUMBING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROPOSED LOCATION OF NEW WATER HEATER IS NOT | | | ALLOWED. SEC. P2801.3 OF 2010 FBC-RESIDENTIAL. PROPOSED | | | LOCATION DOESN'T ALLOW FOR INSPECTION SERVICE, REPAIR | | | AND REPLACEMENT. SEE SEC. M1305. REVISE PLANS AS | | | REQUIRED. | | | | | | 2- REVISE PLUMBING RISER DIAGRAM. EACH WET-VENTED | | | FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE | | | HORIZONTAL WET VENT AS REQUIRED BY SEC. P3108.1 OF 2010 | | | FBC-RESIDENTIAL. BATHROOM TUB DRAIN NEEDS TO CONNECT | | | DIRECTLY TO THE HORIZONTAL WET VENT. | | | | | | IF YOU HAVE ANY QUESTION, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|