| 2013-03-19 11:12:21 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- SPECIFY THE CALCULATED DESIGN PRESSURES FOR ALL NEW |
| | WINDOWS AS REQUIRED BY SEC. R301.1 OF FBC-RESIDENTIAL. |
| | ***NOTE: ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING |
| | IS LOCATED IN EXPOSURE "C". TAKE THIS INTO |
| | CONSIDERATION WHEN DOING THE CALCULATIONS. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR ALL STRUCTURAL FASTENERS SPECIFIED ON |
| | THE FRAMING DETAILS REQUESTED ON ITEM #2 ABOVE. |
| | ***NOTE; PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE |
| | AND PAGE SHOWING THE SPECIFIED CONNECTOR. |
| | |
| | 3- SPECIFY ALL HURRICANE CONNECTORS AT THE ENDS OF THE |
| | EACH STRUCTURAL MEMBER IN WINDOW OPENING DETAIL, |
| | SECTION A AND SECTION B DETAILS TO VERIFY COMPLIANCE |
| | WITH THE WIND LOADS OF SEC. R301.2.1.4.3. |
| | |
| | 4- DESIGN OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | THE WINDOW PRODUCT APPROVALS AND THE STRUCTURAL |
| | CONNECTORS SPECIFIED ON FRAMING DETAILS AS REQUIRED BY |
| | SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| | |
| | 5- PROVIDE MANUFACTURER'S CUT SHEETS FOR THE BEDROOM |
| | EGRESS WINDOW SIZE SPECIFIED ON PLANS TO VERIFY |
| | COMPLIANCE WITH SEC. R310. NOA 06-0608.03 SUBMITTED |
| | DON'T SHOW SIZES AND SHOWS SINGLE HUNG WINDOW WITH THE |
| | LOWER SASH SMALLER THAN THE TOP. NEED TO VERIFY EGRESS |
| | CLEAR OPENING. |
| | |