| 2013-03-15 15:53:30 | BUILDING PLAN REVIEW |
| | PERMIT: 13020302 |
| | ADD: 426 10TH ST |
| | CONT: RECORD CONSTRUCTION |
| | TEL: (561)662-2775 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | MARCH 15/2013 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) SEMI-COMPLIED. PLEASE RATE THE 2ND STORY EXIT |
| | CORRIDOR, ONLY ONE SIDE IS INDICATED AS A NEW RATED |
| | WALL.FIRST FLOOR AND SECOND FLOOR. INCLUDING THE UNDER |
| | SIDE OF THE STAIR STRINGER. PLEASE PROVIDE EITHER A |
| | GYPSUM OR UL LISTING FOR RATED WALL (FIRE PARTITIONS) |
| | FBC-B 709.4 AND FLOOR SYSTEMS, (FIRE BARRIERS) FBC-B |
| | 707.3 FIRE-RESISTANCE RATING & 439.3 HORIZONTAL |
| | SEPERATION. THE FIRE-RESISTANCE RATING OF FIRE BARRIERS |
| | SHALL COMPLY WITH THIS SECTION. |
| | 2010 707.5 CONTINUITY. FIRE BARRIERS SHALL EXTEND FROM |
| | THE TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY |
| | BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, |
| | SLAB OR DECK ABOVE AND SHALL BE SECURELY ATTACHED |
| | THERETO. SUCH FIRE BARRIERS SHALL BE CONTINUOUS THROUGH |
| | CONCEALED SPACES, SUCH AS THE SPACE ABOVE A SUSPENDED |
| | CEILING. |
| | 707.7 PENETRATIONS.PENETRATIONS OF FIRE BARRIERS SHALL |
| | COMPLY WITH SECTION 713. |
| | 707.7.1 PROHIBITED PENETRATIONS. PENETRATIONS INTO AN |
| | EXIT ENCLOSURE OR AN EXIT PASSAGEWAY SHALL BE ALLOWED |
| | ONLY WHEN PERMITTED BY SECTION 1022.4 OR 1023.6, |
| | RESPECTIVELY. |
| | 707.8 JOINTS. JOINTS MADE IN OR BETWEEN FIRE BARRIERS, |
| | AND JOINTS MADE AT THE INTERSECTION OF FIRE BARRIERS |
| | WITH UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR |
| | DECK ABOVE, SHALL COMPLY WITH SECTION 714. |
| | |
| | 3)SEMI-NEW COMMENT RESTATED FOR A 1 & 2 FAMILY |
| | DWELLING: R314.2 SMOKE DETECTION SYSTEMS R314.3 |
| | LOCATION. |
| | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | 1. IN EACH SLEEPING ROOM. |
| | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS. |
| | 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| | BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL |
| | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| | |
| | NOTE IF THERE IS FOSSIL FUEL BURNING HEATERS, FIREPLACE |
| | OR APPLIANCE S THEN R315 CARBON MONOXIDE ALARMS ARE |
| | REQUIRED. |
| | R315.1 CARBON MONOXIDE PROTECTION. |
| | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| | AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| | ROOM USED FOR SLEEPING PURPOSES. |
| | EXCEPTION: THIS SECTION SHALL NOT APPLY TO EXISTING |
| | BUILDINGS THAT ARE UNDERGOING ALTERATIONS OR REPAIR |
| | UNLESS THE ALTERATION IS AN ADDITION AS DEFINED IN |
| | SECTION R315.1.3. |
| | R315.1.1 CARBON MONOXIDE ALARM. |
| | THE REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED |
| | BY PROVIDING FOR ONE OF THE FOLLOWING ALARM |
| | INSTALLATIONS: |
| | (1) A HARD-WIRED CARBON MONOXIDE ALARM. |
| | (2) A BATTERY-POWERED CARBON MONOXIDE ALARM. |
| | (3) A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE |
| | ALARM. |
| | (4) A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND |
| | SMOKE ALARM. |
| | R315.1.2 COMBINATION ALARMS. |
| | COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE |
| | LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE |
| | INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM |
| | DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT |
| | THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE |
| | ALARMS IN THE INDIVIDUAL UNIT. |
| | |
| | |
| | 4) COMPLIED. |
| | |
| | 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6) THE DOOR APPROVAL FL 11321-R1 IS ONLY LISTED AS |
| | TESTED FOR LARGE MISSILE IMPACT, NO RATING FOR |
| | PRESSURES. |
| | |
| | 7-9) COMPLIED. |
| | |
| | 10) SEMI-COMPLIED. THE PLANS NOW SHOW ATTIC ACCESS WITH |
| | A LIGHT FIXTURE ON THE REMOVALABLE LID, HOW WILL THE |
| | WIRE HAVE FLEX TO ALLOW FOR THE REMOVAL OF THE ACCESS |
| | HATCH. ATTIC ACCESS NOT SHOWN. 2010 FBC-B 1209.2 ATTIC |
| | SPACES. AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES |
| | (559 MM BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA |
| | HAVING A CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A |
| | 30-INCH (762 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC |
| | SPACE SHALL BE PROVIDED AT OR ABOVE THE ACCESS OPENING. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) NOT REQUIRED. |
| | |
| | |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |