| 2013-02-16 12:52:20 | 426 10TH STREET |
| | PERMIT #13020302 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NO PERMIT RECORDS COULD BE LOCATED INDICATING THIS |
| | SINGLE FAMILY HOME WAS CONVERTED TO AN APARTMENT |
| | BUILDING; THEREFORE, A PERMIT FOR A CHANGE OF OCCUPANCY |
| | NEEDS TO BE SUBMITTED. |
| | |
| | PLANS, INCLUDING EXIT STAIRS, SHALL BE DESIGNED IN |
| | ACCORDANCE WITH NFPA 101 - LIFE SAFETY CODE (2009 |
| | EDITION WITH FLORIDA AMENDMENTS) CHAPTER 30 TITLED, |
| | "NEW APARTMENTS." |
| | |
| | EXIT ENCLOSURES AND EXIT ENCLOSURE DOORS SHALL HAVE A |
| | MINIMUM 1-HOUR FIRE RESISTANCE RATING PER NFPA 101 |
| | SECTION 30.2.2.1.2. |
| | |
| | PER NFPA 101 SECTION 30.3.5, NEW APARTMENT BUILDINGS |
| | SHALL BE PROTECTED BY AN APPROVED, SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM. ENGINEERED FIRE SPRINKLER |
| | CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL |
| | BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN |
| | ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP |
| | DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION |
| | DOCUMENTS) FOR A SUB-PERMIT. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |