| 2013-02-21 12:33:35 | 13020302 |
| | 426 10TH STREET |
| | MULTIFAMILY RENOVATION |
| | |
| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | ELECTRICAL REVIEW COMMENTS. |
| | |
| | PROVIDE AN ELECTRICAL RISER PLAN WITH A SINGLE SERVICE |
| | MAST AND SHOWING THE APPROPRIATE WIRE SIZES, METERS AND |
| | DISCONNECTS. INCLUDE A SUMMARY LOAD CALCULATION FOR THE |
| | ELECTRIC SERVICE. NEC 215.5 |
| | |
| | A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED |
| | BY ONLY ONE SERVICE. NEC 230.2 |
| | |
| | MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN |
| | A BUILDING. NEC 230.70 |
| | |
| | THE SERVICE DISCONNECTING MEANS SHALL CONSIST OF NOT |
| | MORE THAT SIX SWITCHES. NEC 230.71 |
| | |
| | THE TWO TO SIX DISCONNECTS AS PERMITTED SHALL BE |
| | GROUPED IN ONE LOCATION. NEC 230.72 |
| | |
| | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| | SERVICE GROUND. NEC 250.94 |
| | |
| | INDICATE THE FAULT CURRENT CAPABILITY OF THE ELECTRICAL |
| | SERVICE DISCONNECTS AND PANEL BOARDS. NEC 110.9 |
| | |
| | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 |
| | |