Plan Review Notes
Plan Review Notes For Permit 13020302
Permit Number 13020302
Review Stop E
Sequence Number 1
Notes
Date Text
2013-02-21 12:33:3513020302
 426 10TH STREET
 MULTIFAMILY RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL RISER PLAN WITH A SINGLE SERVICE
 MAST AND SHOWING THE APPROPRIATE WIRE SIZES, METERS AND
 DISCONNECTS. INCLUDE A SUMMARY LOAD CALCULATION FOR THE
 ELECTRIC SERVICE. NEC 215.5
  
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE. NEC 230.2
  
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING. NEC 230.70
  
 THE SERVICE DISCONNECTING MEANS SHALL CONSIST OF NOT
 MORE THAT SIX SWITCHES. NEC 230.71
  
 THE TWO TO SIX DISCONNECTS AS PERMITTED SHALL BE
 GROUPED IN ONE LOCATION. NEC 230.72
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 INDICATE THE FAULT CURRENT CAPABILITY OF THE ELECTRICAL
 SERVICE DISCONNECTS AND PANEL BOARDS. NEC 110.9
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  