2013-02-20 08:34:35BUILDING PLAN REVIEW
 PERMIT: 13020302
 ADD: 426 10TH ST
 CONT: RECORD CONSTRUCTION
 TEL: (561)662-2775
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 FEB. 20/2013
 ACTION: DENIED
  
 1) THE CITY RECORDS INDICATE THIS PROPERTY IS LICENSED
 AS A 2 UNIT RENTAL, ADDING A THIRD UNIT WILL CREATE A
 CHANGE IN OCCUPANCY FROM A 1 & 2 FAMILY R-3 TO A 3 UNIT
 R-2 WHICH IS REVIEWED BY THE 2010 FBC-B & THE 2010
 EXISTING BLDG CODE. 2010 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A
 BUILDING CHANGES, THE PROVISIONS OF SECTIONS 902
 THROUGH 912 SHALL APPLY. THIS INCLUDES A CHANGE OF
 OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A
 CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A
 DIFFERENT GROUP. EXT BLDG CODE 904.1 GENERAL.FIRE
 PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY
 WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE
 OF OCCUPANCY CLASSIFICATION.EXT BLDG CODE 912.2 FIRE
 PROTECTION SYSTEMS. FIRE PROTECTION SYSTEMS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTIONS 912.2.1 AND
 912.2.2. EXT BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS. 2010 FBC-B F] 903.2.8 GROUP
 R. AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH SECTION 903.3 SHALL BE PROVIDED
 THROUGHOUT ALL BUILDINGS WITH A GROUP R FIRE AREA.\
  
 2) PLEASE PROVIDE EITHER A GYPSUM OR UL LISTING FOR
 RATED WALL (FIRE PARTITIONS) FBC-B 709.4 AND FLOOR
 SYSTEMS, (FIRE BARRIERS) FBC-B 707.3 FIRE-RESISTANCE
 RATING & 439.3 HORIZONTAL SEPERATION. THE
 FIRE-RESISTANCE RATING OF FIRE BARRIERS SHALL COMPLY
 WITH THIS SECTION.
 2010 707.5 CONTINUITY. FIRE BARRIERS SHALL EXTEND FROM
 THE TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY
 BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING,
 SLAB OR DECK ABOVE AND SHALL BE SECURELY ATTACHED
 THERETO. SUCH FIRE BARRIERS SHALL BE CONTINUOUS THROUGH
 CONCEALED SPACES, SUCH AS THE SPACE ABOVE A SUSPENDED
 CEILING.
 707.7 PENETRATIONS.PENETRATIONS OF FIRE BARRIERS SHALL
 COMPLY WITH SECTION 713.
 707.7.1 PROHIBITED PENETRATIONS. PENETRATIONS INTO AN
 EXIT ENCLOSURE OR AN EXIT PASSAGEWAY SHALL BE ALLOWED
 ONLY WHEN PERMITTED BY SECTION 1022.4 OR 1023.6,
 RESPECTIVELY.
 707.8 JOINTS. JOINTS MADE IN OR BETWEEN FIRE BARRIERS,
 AND JOINTS MADE AT THE INTERSECTION OF FIRE BARRIERS
 WITH UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR
 DECK ABOVE, SHALL COMPLY WITH SECTION 714.
 PLEASE RATE THE 2ND STORY EXIT CORRIDOR, ONLY ONE SIDE
 IS INDICATED AS A NEW RATED WALL.FIRST FLOOR AND SECOND
 FLOOR. INCLUDING THE UNDER SIDE OF THE STAIR STRINGER.
  
 3) 2010 EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION
 SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION
 OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM
 TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE
 WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING,
 SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE
 THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM
 NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY
 ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING
 IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM
 NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT
 THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL
 BE AUTOMATICALLY ACTIVATED.
 2010 FBC-B F] 907.2.9 GROUP R-2. FIRE ALARM SYSTEMS AND
 SMOKE ALARMS SHALL BE INSTALLED IN GROUP R-2
 OCCUPANCIES AS REQUIRED IN SECTIONS 907.2.9.1 AND
 907.2.9.2.
  
 4) SHEET A-1 UNIT NUMBER 3 IS INDICATED AS A 2 BEDROOM
 BUT THERE IS ONLY ONE BEDROOM THE OTHER ROOM IS TO
 SMALL FOR A BEDROOM AND IS LABELED A SEWING ROOM,
 PLEASE UPDATE THIS DISCREPANCY. 107.2.1.3. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) THE DOOR APPROVAL FL 11321-R1 IS ONLY LISTED AS
 TESTED FOR LARGE MISSILE IMPACT, NO RATING FOR
 PRESSURES.
  
 7) THE PRESSURES LISTED ON THE PLANS DO NOT INDICATE IF
 THESE ARE FOR WALL ZONES INTERIOR ZONES OR FOR THE ZONE
 5 CORNER ZONES, THE PLANS DEPICT OPENINGS WITHIN BOTH
 ZONES, PLEASE PROVIDE PRESSURES FOR BOTH ZONES.
 COMPONENTS AND CLADDING.
  
 8) SHEET A1 INDICATES THIS BUILDING AS A TYPE V
 CONSTRUCTION, PLEASE SEE 2010 FBC-B TABLE 503 EITHER VA
 OR VB.
  
 9) THE WINDOW PRODUCT APPROVAL PLEASE CIRCLE THE WINDOW
 SIZES TO BE INSTALLED, TYPE OF GLAZING, AND PRESSURES,
 PLEASE ALSO IDENTIFY WHICH OF THE MULLION SIZES THAT
 ARE TO BE INSTALLED. COMPONENT & CLADDING VS PRESSUES.
  
 10) ATTIC ACCESS NOT SHOWN. 2010 FBC-B 1209.2 ATTIC
 SPACES.
 AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM
 BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A
 CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762
 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT OR ABOVE THE ACCESS OPENING.
  
 11) 1210.3 SHOWERS. SHOWER COMPARTMENTS AND WALLS ABOVE
 BATHTUBS WITH INSTALLED SHOWER HEADS SHALL BE FINISHED
 WITH A SMOOTH, NONABSORBENT SURFACE TO A HEIGHT NOT
 LESS THAN 70 INCHES (1778 MM) ABOVE THE DRAIN INLET.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  