| 2013-02-12 12:14:35 | 428 10TH STREET | | | PERMIT #13020274 | | | MASTER #12060308 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO - SUBMIT REVISION***** | | | | | | FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED | | | SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. | | | | | | PROVIDE A LOCAL WATERFLOW ALARM TO ALERT BUILDING | | | OCCUPANTS. | | | | | | INDICATE THE PIPE TYPE TO BE USED FOR THE UNDERGROUND | | | INSTALLATION. | | | | | | SPRINKLER DESIGN SHALL CONFORM TO THE 2007 EDITION OF | | | NFPA 13R IN LIEU OF THE 2002 EDITION INDICATED ON THE | | | PLANS. | | | | | | ADD THE DOMESTIC WATER DEMAND TO THE OVERALL SYSTEM | | | DEMAND SHOWN IN THE HYDRAULIC CALCULATIONS. | | | | | | SUBMIT PRODUCT DATA FOR BACKFLOW PREVENTER, CPVC PIPE, | | | AND SPRINKLERS. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|