| 2013-03-10 17:48:35 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) ON SHEET 7 OF 9 THE WALL SECTIONS SHOW SPRAY FOAM |
| | INSULATION AND SPECIFY SOFFIT VENTS AND THE ENERGY |
| | CALCULATIONS SPECIFY AN UNVENTED ATTIC. PLEASE CLARIFY. |
| | CITY AMENDMENTS 107.2.1 |
| | |
| | 2) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE |
| | SPRAY FOAM INSULATION THAT WILL BE INSTALLED. FBCR 316 |
| | |
| | 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS, AS REQUIRED |
| | BY DCA RULE 9N-3, FOR THE STRUCTURAL MULLIONS, FIXED |
| | GLASS WINDOWS, AND THE WOOD FRONT DOOR ( A CUSTOM DOOR |
| | REQUIRES SITE SPECIFIC ENGINEERING). |
| | |
| | 4) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| | SLIDING GLASS DOOR, REQUIRES THE DOOR TO HAVE IMPACT |
| | PROTECTION. SUBMIT TWO COPIES OF THE PRODUCT APPROVAL |
| | FOR THE IMPACT PROTECTION SYSTEM THAT WILL BE INSTALLED |
| | FOR THIS DOOR. PROVIDE AN INSTALLATION SCHEDULE |
| | SPECIFYING THE TYPE OF MOUNT, THE FASTENER TYPE, |
| | FASTENER SPACING, PANEL SPAN, GLASS SEPARATION AND ANY |
| | OTHER INFORMATION FROM THE PRODUCT APPROVAL TO |
| | DETERMINE THAT THE INSTALLATION WILL BE CODE COMPLIANT. |
| | FBCR301.2.1.2 |
| | |
| | 5) THE PRODUCT APPROVAL SUBMITTED FOR THE SINGLE HUNG |
| | WINDOWS HAS MAXIMUM DESIGN PRESSURES OF + 60, - 60 PSF. |
| | THE SINGLE HUNG WINDOW IN THE SECOND FLOOR BATHROOM HAS |
| | A NEGATIVE PRESSURE OF - 69.6 PSF WHICH IS MORE THAN |
| | THE PROPOSED WINDOW IS RATED FOR. PLEASE PROVIDE A |
| | PRODUCT APPROVAL THAT MEETS THE WINDLOAD REQUIREMENTS |
| | FOR THIS WINDOW AS REQUIRED BY FBCR 301.2.1. |
| | |
| | 6) ALL OF THE ADDITIONAL PRODUCT APPROVALS THAT |
| | SUBMITTED ARE REQUIRED TO BE REVIEWED AND APPROVED BY |
| | THE DESIGNER OF RECORD. CITY AMENDMENTS 107.3.4.1 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |