2013-03-16 17:24:08429 BELVEDERE ROAD
 PERMIT #13020224
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES REMODEL WORK ON BOTH
 THE FIRST AND SECOND FLOOR; HOWEVER, NO WORK IS BEING
 SHOWN ON THE FIRST FLOOR.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 THE RESIDENTIAL OCCUPANCY IS REQUIRED TO BE SEPARATED
 FROM OTHER OCCUPANCY TYPES WITH AT LEAST A 2-HOUR
 FIRE-RATED BARRIER. NO FLOOR/CEILING FIRE RATING IS
 INDICATED. PENETRATIONS SHALL BE PROTECTED WITH A
 LISTED ASSEMBLY.
  