Plan Review Notes
Plan Review Notes For Permit 13020224
Permit Number 13020224
Review Stop E
Sequence Number 1
Notes
Date Text
2013-03-07 10:52:3713020224
 429 BELVEDERE ROAD
 APARTMENT INTERIOR REMODEL
 CHANGE OF USE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
  
 VERIFY ALL EXTERIOR SERVICE EQUIPMENT IS RATED FOR A
 WET LOCATION. NEC 306.9
  
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH
 PROTECTION, HIGH-LEG MARKING AT THE PANEL BOARDS AND
 THE MAIN DISCONNECTING MEANS. NEC 110.22, 110.16,
 110.22
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED ON THE ROOF FOR
 SERVICING THE AIR CONDITIONING EQUIPMENT. NEC 210.63,
 210.8(B)
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH
 CIRCUITS. NEC 210.52
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  