| 2013-03-07 10:52:37 | 13020224 | | | 429 BELVEDERE ROAD | | | APARTMENT INTERIOR REMODEL | | | CHANGE OF USE | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | | ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10 | | | | | | VERIFY ALL EXTERIOR SERVICE EQUIPMENT IS RATED FOR A | | | WET LOCATION. NEC 306.9 | | | | | | PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH | | | PROTECTION, HIGH-LEG MARKING AT THE PANEL BOARDS AND | | | THE MAIN DISCONNECTING MEANS. NEC 110.22, 110.16, | | | 110.22 | | | | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED ON THE ROOF FOR | | | SERVICING THE AIR CONDITIONING EQUIPMENT. NEC 210.63, | | | 210.8(B) | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | | | PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH | | | CIRCUITS. NEC 210.52 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|