| 2013-04-01 12:40:27 | | | | 13020219 | | | 817 21ST STREET | | | RESIDENTIAL REPAIR | | | | | | THE PERMIT WAS APPROVED WITH THE FOLLOWING REQUIREMENTS | | | LISTED ON THE PLAN. | | | | | | PROVISO | | | | | | KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI PROTECTED. | | | NEC 210.8 | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | | | THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE | | | FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1) | | | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. NEC 250.94 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|