| 2013-02-12 11:37:22 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | |
| | 1. SEE FBC 107.2.1: |
| | |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE |
| | MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED |
| | WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | NO PLAN SUBMITTED. |
| | |
| | 2. PLEASE DO NOT SUBMIT DOCUMENTS NOT REQUIRED TO SHOW |
| | CODE COMPLIANCE. FOR INSTANCE, THE DOCUMENT REGARDING |
| | LEAD BASED PAINT. |
| | |
| | 3. PROVIDE A STRUCTURAL DETAILS FOR STAIRS, RAILINGS, |
| | COLUMNS, NEW INTERIOR DOOR FRAMING (AS WELL AS INCLUDE |
| | LOCATIONS ON A FLOOR PLAN), FBC R 301. |
| | |
| | 4. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR |
| | THE DOORS AND WINDOWS, FAC9N-3. |
| | |
| | 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPOVAL FOR |
| | THE FLAT DECK. PROVIDE ROOF HEIGHT AND SLOPE. FOR THE |
| | ROOF, INDICATE WHICH APPROVED ASSEMBLY IS PROPOSED AND |
| | PROVIDE ENGINEERING IF REQUIRED OR OTHERWISE SPECIFY |
| | ENHANCED FASTENING, SEE LIMITATIONS ON THE PRODUCT |
| | APPROVAL. A SEPARATE ROOF SUB PERMIT IS REQUIRED. |
| | |
| | PLEASE NOTE THAT INSULATION BOARD IS REQUIRED PER |
| | SPECIFICATION. |
| | |
| | ROOF INFORMATION MAY BE PROVIDED UNDER A SEPARATE STAND |
| | ALONE PERMIT. PLEASE ADVISE IF YOU WISH FOR THIS SCOPE |
| | TO BE REMOVED FROM THIS PERMIT. |
| | |
| | 6. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING |
| | CANNOT BE REDUCED BY MORE THAN 5%. INCLUDE DOOR |
| | LOCATIONS FOR DOORS TO BE REPLACED AS WELL AS DOOR |
| | SIZE. |
| | |
| | 7. REAR UNIT REQUIRES ALL INFORMATION AS NOTED ABOVE TO |
| | BE INCLUDED IN A SEPARATE PERMIT APPLICATION. |
| | |
| | |
| | |