2013-08-26 16:14:13PROVIDE INTERSYSTEM BONDING POINT AT SERVICE 250.94
 BATHROOM RECEPTACLE CIRCUIT TO BE 20 AMP RATED 210.11 C
 3
 SEE 210.52 C 3&5 FOR PENINSULAR COUNTER TO ENSURE
 COMPLIANCE
 PLANS SPECIFY "CONDUIT" FOR THE WIRING METHOD. PLEASE
 CONFIRM
 PLANS CALL FOR FOUNDATION STEEL TO BE ATTACHED TO THE
 GROUNDING ELECTRODE SYSTEM. THIS A RENOVATION. IS
 FOOTER STEEL AVAILABLE?
 SMOKE/CO ALARMS SHOULD BE LOCATED PERMANUFACTURERS
 INSTRUCTIONS AND TO PROVIDE THE BEST COVERAGE, NOT
 NECESSARILY AT THE BEDROOM ENTRY. 110.3
 EGRESS LIGHT IS REQUIRED AT FRONT DOOR (FAN IS NOT
 ILLUMINATION) 210.70
 PLEASE PROVIDE AVAIALBLE FAULT CURRENT AT THE SERVICE
 TO ENSURE COORDINATION OF ELECTRICAL EQUIPMENT 110.9
  