| Plan Review Notes For Permit 13020217 |
| Permit Number |
13020217 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-08-26 16:14:13 | PROVIDE INTERSYSTEM BONDING POINT AT SERVICE 250.94 | | | BATHROOM RECEPTACLE CIRCUIT TO BE 20 AMP RATED 210.11 C | | | 3 | | | SEE 210.52 C 3&5 FOR PENINSULAR COUNTER TO ENSURE | | | COMPLIANCE | | | PLANS SPECIFY "CONDUIT" FOR THE WIRING METHOD. PLEASE | | | CONFIRM | | | PLANS CALL FOR FOUNDATION STEEL TO BE ATTACHED TO THE | | | GROUNDING ELECTRODE SYSTEM. THIS A RENOVATION. IS | | | FOOTER STEEL AVAILABLE? | | | SMOKE/CO ALARMS SHOULD BE LOCATED PERMANUFACTURERS | | | INSTRUCTIONS AND TO PROVIDE THE BEST COVERAGE, NOT | | | NECESSARILY AT THE BEDROOM ENTRY. 110.3 | | | EGRESS LIGHT IS REQUIRED AT FRONT DOOR (FAN IS NOT | | | ILLUMINATION) 210.70 | | | PLEASE PROVIDE AVAIALBLE FAULT CURRENT AT THE SERVICE | | | TO ENSURE COORDINATION OF ELECTRICAL EQUIPMENT 110.9 | | | |
|