| 2013-08-22 19:26:51 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1-2. OK |
| | |
| | 3. PROVIDE A STRUCTURAL DETAILS FOR GABLE REPAIR (SEE |
| | FBC R 703.6.3 REGARDING BOND BREAK). GABLE BRACING, |
| | SHOW SOFFIT VENTILATION. |
| | |
| | 2ND REVIEW, DETAIL PROVIDED BUT PLEASE REVISE PER FBC |
| | 2010 RESIDENTIAL 703.6.3, BOND BREAK REQUIRED. |
| | |
| | 4. OK |
| | |
| | 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPOVAL FOR |
| | THE SINGLES AND THE FLAT DECK. PROVIDE ROOF HEIGHT AND |
| | SLOPE. FOR THE ROOF, INDICATE WHICH APPROVED ASSEMBLY |
| | IS PROPOSED AND PROVIDE ENGINEERING IF REQUIRED OR |
| | OTHERWISE SPECIFY ENHANCED FASTENING, SEE LIMITATIONS |
| | ON THE PRODUCT APPROVAL. A SEPARATE ROOF SUB PERMIT IS |
| | REQUIRED. |
| | |
| | 2ND REVIEW, WIND SPEED MINIMUM PER |
| | WWW.ATCOUNCIL.ORG/WINDSPEED SHOULD BE 169MPH. PLAN |
| | STATES DESIGN CRITEIA IS 165MPH, S100. PRESSURES APPEAR |
| | LOW. EITHER CONTACT ME TO INFORM HOW WIND SPEED WAS |
| | DETERMINED OR REVISE DESIGN CRITERIA AND DESIGN |
| | PRESSURES ACCORDINGLY. |
| | |
| | THE RAS117 CALCULATIONS ON S200 REFER TO 07-1219.09, |
| | BUT THE NOA REVIEWED BY ARCHITECT AND SUBMITTED BY |
| | CONTRACTOR IS 07-1219.09. |
| | |
| | 6-8. OK |
| | |
| | NEW COMMENTS BASED ON NEW PLAN PROVIDED: |
| | |
| | 9. S100, A/C SLAB SHOWN SMALLER THAN THE UNIT. NO |
| | FASTENING OF UNIT TO SLAB SPECIFIED. PLEASE REVISE, FBC |
| | 2010 RESIDENTIAL 301. |
| | |
| | 10. PROVIDE A DETAIL FOR BLOCK INFILL SHOWN ON A-100 |
| | (BR1, BR2, KITCHEN). FBC 107, FBC 2010 RESIDENTIAL 301. |
| | |
| | 11. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY |
| | REQUIRED. THE PLANS ARE TO BE STAMPED AND THE RECEIPT, |
| | IF FEES WERE DUE, TO BE SUBMITTED AS EVIDENCE THAT THE |
| | FEES WERE PAID. 233-5025 FOR MORE INFORMATION |
| | |
| | **UPON REQUEST, ALL ITEMS CAN BE PROVISO ITEMS - |
| | REVISION REQUIRED (WITH FEES), ISSUED AT CONTRACTOR'S |
| | RISK** |
| | |
| | |
| | |
| | |