| 2013-04-22 14:10:50 | 701 SOUTH ROSEMARY AVENUE - SUITE #316 |
| | PERMIT #13020210 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | RESPONSE COMMENT: RELIANCE ON THE TENANT TO MAINTAIN |
| | CLEAR AISLES HAS NOT BEEN SUCCESSFUL. PLEASE PROVIDE |
| | FLOOR MARKINGS, BOLLARDS, OR DIFFERENT FLOORING |
| | MATERIAL SO EGRESS AISLES WILL ALWAYS BE READILY |
| | IDENTIFIABLE NO MATTER HOW THE MERCHANDISE AND DISPLAYS |
| | CHANGE. |
| | ORIGINAL COMMENT: SHEET A-100: PLANS STATE THAT A CLEAR |
| | WIDTH OF 3'-0" AND 3'-8" IS TO BE MAINTAINED FOR |
| | EXITING; PLEASE INDICATE HOW THIS WILL BE ACCOMPLISHED |
| | AND MAINTAINED. |
| | |
| | RESPONSE COMMENT: THE FIRE PROTECTION INFORMATION FROM |
| | THE ORIGINAL COMMENT NEEDS TO BE SUBMITTED EVEN IF THE |
| | DESIGN IS A PERFORMANCE SPECIFICATION. FOR ISSUANCE OF |
| | A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE |
| | FLORIDA BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| | CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF |
| | 50 OR MORE AUTOMATIC FIRE SPRINKLERS. AFTER THE |
| | BUILDING PERMIT HAS BEEN ISSUED, THE SPRINKLER |
| | CONTRACTOR CAN THEN SUBMIT SHOP DRAWINGS (CONFORMING TO |
| | THE ENGINEERED CONSTRUCTION DOCUMENTS) FOR A |
| | SUB-PERMIT. |
| | ORIGINAL COMMENT: SHEET FP-210: PER FLORIDA |
| | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |