| Plan Review Notes For Permit 13020210 |
| Permit Number |
13020210 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-03-12 14:41:28 | ****CORRECTIONS**** | | | | | | 1. REVISE PLAN TO SHOW HOW DUCTWORK WILL BE ROUTED | | | THROUGH TWO STORIES OF EXISTING APARTMENTS TO THE | | | PROPOSED NEW RTUS. | | | | | | 2. REVISE THE CURB DETAIL ON SHEET 301.12 TO SPECIFY | | | FASTENERS, FBC MECHANICAL 301.12. | | | | | | HAROLD MOSER, MECHANICAL PLANS EXAMINER | | | 561-805-6732 | | | | | | | | | | | | | | | |
|