| Plan Review Notes For Permit 13020137 |
| Permit Number |
13020137 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-07 14:30:38 | RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL4930-R4 | | | SUBMITTED: | | | A) DESIGN PRESSURES FOR SELECTED ASSEMBLY (S-92) ARE | | | TOO LOW. PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS | | | AS REQUIRED BY NOTE #9 TO MEET THE DESIGN PRESSURES | | | REQUIRED BY SEC. 1609.4.2 OF 2010 FBC. (PROVIDE TWO | | | ORIGINAL SIGNED AND SEALED COPIES AND DESIGN | | | PROFESSIONAL TO COORDINATE WITH ITEM # 1(B) BELOW). | | | | | | ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO | | | TAKE INTO CONSIDERATION THAT ACCORDING TO SEC. 1609.4.2 | | | THIS BUILDING IS LOCATED IN EXPOSURE "C". | | | | | | B) PROVIDE FASTENER UPLIFT TESTING (TAS 105) AS | | | REQUIRED BY NOTE #11 OF FLORIDA PRODUCT APPROVAL | | | SUBMITTED. (PROVIDE TWO ORIGINAL SIGNED AND SEALED | | | COPIES) | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|