2013-02-07 14:30:38RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL4930-R4
 SUBMITTED:
 A) DESIGN PRESSURES FOR SELECTED ASSEMBLY (S-92) ARE
 TOO LOW. PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 AS REQUIRED BY NOTE #9 TO MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. 1609.4.2 OF 2010 FBC. (PROVIDE TWO
 ORIGINAL SIGNED AND SEALED COPIES AND DESIGN
 PROFESSIONAL TO COORDINATE WITH ITEM # 1(B) BELOW).
  
 ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO
 TAKE INTO CONSIDERATION THAT ACCORDING TO SEC. 1609.4.2
 THIS BUILDING IS LOCATED IN EXPOSURE "C".
  
 B) PROVIDE FASTENER UPLIFT TESTING (TAS 105) AS
 REQUIRED BY NOTE #11 OF FLORIDA PRODUCT APPROVAL
 SUBMITTED. (PROVIDE TWO ORIGINAL SIGNED AND SEALED
 COPIES)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL