| 2013-03-06 15:35:06 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE EXPOSURE CATEGORY IS INCORRECTLY SPECIFIED AS B. |
| | THE CORRECT EXPOSURE CATEGORY IS C PER FBCR |
| | 301.2.1.4.3. PLEASE CORRECT THE PLANS AND INCREASE THE |
| | WINDLOAD PRESSURES FOR THE WINDOWS, DOORS AND OTHER |
| | COMPONENTS AND CLADDING ACCORDINGLY. FBCR 301.2.1 |
| | |
| | 2) ON THE TYPICAL WALL SECTION ON SHEET A3, THE NOTE |
| | SPECIFIES ICYNENE SPRAY FOAM INSULATION AND NO ATTIC |
| | VENTS ARE SHOWN. THE ENERGY CALCULATIONS SPECIFY A |
| | VENTED ATTIC AND THE SCOPE OF WORK SPECIFIES R-30 |
| | FIBERGLASS BATTS. PLEASE CLARIFY AND MAKE ANY NECESSARY |
| | CORRECTIONS. CITY AMENDMENTS 107.2.1 |
| | |
| | 3) SUBMIT TWO COPIES OF THE EVALUATION REPORTS FOR THE |
| | ICYNENE SPRAY FOAM INSULATION.FBCR 316.3 |
| | |
| | 4) ON THE TYPICAL WALL SECTION ON SHEET A3, THE MINIMUM |
| | WALL INSULATION IS SPECIFIED AS R5 AND THE ENERGY |
| | CALCULATIONS LIST R4.1 WALL INSULATION. PLEASE CLARIFY. |
| | CITY AMENDMENTS 107.2.1 |
| | |
| | 5) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | ROOF TILES OR OTHER ROOF COVERING AS REQUIRED BY DCA |
| | RULE 9N-3. SPECIFY THE ATTACHMENT METHOD THAT WILL BE |
| | USED TO INSTALL THE ROOF TILE AND RESIST THE |
| | OVERTURNING MOMENT. FBCR 905.3 |
| | |
| | 6) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED BY THE DESIGNER OF RECORD. CITY AMENDMENTS |
| | 107.3.4.1 |
| | |
| | 7) SHOW COMPLIANCE WITH FBCR 807.1 FOR ATTIC ACCESS AT |
| | THE NEW ADDITION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |