| Plan Review Notes For Permit 13020033 |
| Permit Number |
13020033 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-04 16:58:07 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY WHICH ONE OF THE FASTENING OPTIONS AND | | | DESIGN PRESSURES LISTED ON PAGE 27 OF THE NOA FOR THE | | | GAF MODIFIED ROOF SYSTEM WILL BE USED. FBCR 905.11.3 | | | | | | 2) SUBMIT TWO COPIES OF SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY | | | LIMITATION NUMBER 7 ON PAGE 31 OF THE NOA. FBCR | | | 905.11.3 AND CITY AMENDMENTS 107.2.1.4 | | | | | | 3) PER FBC EXISTING BUILDING SECTION 611.1.1, NOT MORE | | | THAN 25 PER CENT OF THE TOTAL ROOF AREA OR ROOF SECTION | | | OF ANY EXISTING BUILDING OR STRUCTURE SHALL BE | | | REPAIRED, REPLACED OR RECOVERED IN ANY 12 MONTH PERIOD | | | UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF SECTION | | | CONFORMS TO REQUIREMENTS OF THIS CODE. PROVIDE TWO | | | COPIES OF A DIMENSIONED DIAGRAM OF THE ROOF INDICATING | | | THE AREA OF THE PROPOSED REPAIRS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|