| Plan Review Notes For Permit 13020030 |
| Permit Number |
13020030 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-05 11:48:08 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS AND PUMP CURVES FOR THE PROPOSED 1 HP, 2 | | | SPEED POOL PUMP. FBCR 4101.6.3 | | | | | | 2) PLEASE CLARIFY THE SIZES OF THE MAIN DRAIN PIPING | | | INCLUDING THE BRANCH PIPING BETWEEN THE TWO MAIN | | | DRAINS. THE APPROVED PLANS SHOW 3" PIPE FOR THE MAIN | | | DRAIN, SKIMMER AND VACUUM. THE REVISED PLAN SHOWS 2" | | | FOR ALL PIPING. FBCR 4101.6.3 & CITY AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|