 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ENGINEERED CONSTRUCTION DOCUMENTS INDICATE THAT ALL
 AREAS ABOVE THE CEILING ARE COMPOSED OF CONCEALED
 COMBUSTIBLE CONSTRUCTION. AREAS WILL REQUIRE SPRINKLER
 PROTECTION PER 8.15.1 (NFPA 13 - 2007 EDITION).
  
 SPRINKLERS SHALL BE LOCATED WITHIN 3' OF THE PEAKED
 CEILING PER 8.6.4.1.3 (NFPA 13 - 2007 EDITION).
  
 THE KITCHEN AREA HYDRAULIC PLAN DATA INDICATES AN AREA
 OF 1500 SQ.FT. WAS CALCULATED ALTHOUGH THE ACTUAL
 CALCULATION AREA APPEARS TO BE APPROXIMATELY 1100
 SQ.FT. IF THE HYDRAULIC AREA HAS BEEN REDUCED USING THE
 AREA REDUCTION METHOD FOR QUICK RESPONSE SPRINKLERS
 PLEASE INDICATE THIS ON THE PLANS.
  
 THE DINING AREA HYDRAULIC PLAN DATA INDICATES AN AREA
 OF 1500 SQ.FT. WAS CALCULATED ALTHOUGH THE ACTUAL
 CALCULATION AREA APPEARS TO BE APPROXIMATELY 1600
 SQ.FT. HYDRAULIC AREAS SHALL BE INCREASED BY 30% WHEN
 THE CEILING SLOPE EXCEEDS 1 IN 6 PER 11.2.3.2.4 (NFPA
 13 - 2007 EDITION). AFTER THE 30% INCREASE HAS BEEN
 ADDED, THE AREA MAY THEN BE REDUCED USING THE AREA
 REDUCTION METHOD FOR QUICK RESPONSE SPRINKLERS PLEASE
 INDICATE THIS ON THE PLANS.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  