2013-02-05 13:09:49***PROVISO***
  
 NO DIMENTIONS ARE SHOWN FOR THE NEW RESTROOM. 60" CLEAR
 SPACE IS REQUIRED FOR THE WATER CLOSET WITH NO OTHER
 FIXTURES IN THAT SPACE. FBC ACCESSIBILITY 2010 604.3.1
 & 604.3.2
  
 GRAB BARS COMPLYING WITH FBC ACCESSIBILITY 2010 604.5
 ARE REQUIRED IN THE REST ROOM.
  
 THE LOUNGE SINK WILL BE REQUIRED TO HAVE FRONT OR
 PARALLEL APPROACH COMPLYING WITH 606.2 AND HEIGHT OF
 34" A.F.F. MAX. 606.3
  
 A PAN DRAIN IS REQUIRED FOR THE WATER HEATER. FBC
 PLUMBING 504.7.1
  
  