| 2013-02-05 13:09:49 | ***PROVISO*** | | | | | | NO DIMENTIONS ARE SHOWN FOR THE NEW RESTROOM. 60" CLEAR | | | SPACE IS REQUIRED FOR THE WATER CLOSET WITH NO OTHER | | | FIXTURES IN THAT SPACE. FBC ACCESSIBILITY 2010 604.3.1 | | | & 604.3.2 | | | | | | GRAB BARS COMPLYING WITH FBC ACCESSIBILITY 2010 604.5 | | | ARE REQUIRED IN THE REST ROOM. | | | | | | THE LOUNGE SINK WILL BE REQUIRED TO HAVE FRONT OR | | | PARALLEL APPROACH COMPLYING WITH 606.2 AND HEIGHT OF | | | 34" A.F.F. MAX. 606.3 | | | | | | A PAN DRAIN IS REQUIRED FOR THE WATER HEATER. FBC | | | PLUMBING 504.7.1 | | | | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|