| Plan Review Notes For Permit 13010898 |
| Permit Number |
13010898 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-11 11:48:32 | 13010898 | | | 508 52ND STREET | | | RESIDENTIAL REPAIR | | | | | | THE SCOPE OF THE ELECTRICAL WORK WAS NOT ADEQUATELY | | | DESCRIBED. PLEASE PROVIDE A FLOOR PLAN SHOWING THE | | | SCOPE OF WORK INTENDED OR A SEPARATE DOCUMENT ON THE | | | COMPANY LETTER HEAD OUTLINING THE ELECTRICAL WORK | | | PROPOSED. INCLUDE THE FOLLOWING ITEMS WHERE | | | APPROPRIATE. | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | | | GFCI PROTECTION IS REQUIRED FOR ALL OUTDOOR | | | RECEPTACLES. NEC 210.8 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|