 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT (X2): ENGINEERED FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. SECTION 105.3.1.2(2) OF
 THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE
 PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR
 ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER
 FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  