| 2013-02-25 13:09:28 | 550 SOUTH ROSEMARY AVENUE - SUITE #158 | | | PERMIT #13010847 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | REPEAT COMMENT: ENGINEERED FIRE SPRINKLER CONSTRUCTION | | | DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. | | | AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE | | | SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS | | | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) | | | FOR A SUB-PERMIT. SECTION 105.3.1.2(2) OF THE FLORIDA | | | BUILDING CODE REQUIRES SEALED FIRE PROTECTION | | | CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF | | | 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA | | | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE | | | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|