 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 COMMENTS WHICH WERE NOT ADDRESSED ADEQUATELY WITHIN THE
 SECOND SUBMITTAL. IF REQUIRED PLEASE CALL FOR FURTHER
 CLARIFICATION.
  
 INDICATE THE SIZE OF THE PAD MOUNTED TRANSFORMER. NEC
 215.5
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 THE DESIGNER NEEDS TO PROVIDE THE WORDING, SIZE AND
 LOCATIONS FOR ALL ELECTRICAL SAFETY SIGNAGE REQUIRED BY
 THE NATIONAL ELECTRICAL CODE. NEC 110.22, 110.16,
 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY (ON THE PLANS)
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. THE LIGHTING SUMMARY REQUIRED WILL
 SHOW EACH AREA OF USE IN A TABLE FORMAT VERIFYING
 COMPLIANCE WITH THE ENERGY CODE FOR THE AREA AND IN
 TOTAL. FBC ENERGY CONSERVATION 505.3
  
 VERIFY SERVICE CAPACITY FROM THE MAIN SERVICE FOR THIS
 OCCUPANCY BY CALCULATION. INCLUDE EXISTING AND
 POTENTIAL FUTURE OCCUPANCY LOADS WHICH WILL BE SUPPLIED
 FROM THE EXISTING SERVICE. THE EXISTING SERVICE WHICH
 FORMERLY SERVED PREDOMINANTLY BUSINESS USES IS NOW
 BEING UTILIZED FOR SEVERAL NEW OR FUTURE RESTAURANTS.
 SERVICE CAPACITY NEEDS TO BE VERIFIED. NEC 215.2
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER