Plan Review Notes
Plan Review Notes For Permit 13010847
Permit Number 13010847
Review Stop P
Sequence Number 1
Notes
Date Text
2013-02-05 10:13:06FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. THE BAR EQUIPMENT (HAND SINKS, ICE BINS, FLOOR
 DRAINS, BEER RINSE, ETC.) ARE NOT REQUIRED TO BE
 CONNECTED TO THE GREASE SYSTEM. PLEASE CONNECT TO THE
 SANITARY. PLEASE LEAVE THE KITCHEN ON THE INTERCEPTOR.
 FBC 2010 PLUMBING 2010 1003.2 APPROVAL:
 .....WASTES THAT DO NOT REQUIRE TREATMENT OR SEPARATION
 SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR OR
 SEPARATOR.
  
 2. A VENT IS REQUIRED BETWEEN THE LAST 2 WATER CLOSETS
 (THE H.C. CLOSETS) ON THE CIRCUIT VENT SYSTEM.
 911.2 VENT CONNECTION.
 THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE
 SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR
 WASTE.911.2 VENT CONNECTION.
  
 3. SHEET P1.1 THE COLD WATER MAIN WILL BE REQUIRED TO
 BE 1" TO THE LAST FIXTURE IN THE RESTROOMS PER TABLE
 603.1 (OR PLEASE SHOW ALL FLOW CALCULATIONS ON PLAN).
 604.1 GENERAL.
 THE DESIGN OF THE WATER DISTRIBUTION SYSTEM SHALL
 CONFORM TO ACCEPTED ENGINEERING PRACTICE. METHODS
 UTILIZED TO DETERMINE PIPE SIZES SHALL BE APPROVED.
  
 4. PLEASE INCLUDE THE LOCATION AND SIZE OF THE WATER
 HEATER.
 107.3.5.1.3 PLUMBING 5. WATER HEATERS
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  