Plan Review Notes
Plan Review Notes For Permit 13010847
Permit Number 13010847
Review Stop M
Sequence Number 1
Notes
Date Text
2013-02-01 15:22:32MECHANICAL PLANS DENIED
 1) NOTE 21 ON PAGE M1.2 REQUEST THAT YOU PAINT EXPOSED
 DUCT.
 FIBERGLASS, FLEX OR DUCT WRAP CAN NOT BE PAINTED.
 PER SECTION 603.5 NONMETALLIC DUCT. AND THE MANUFACTURE
 OF THE DUCT .
 2) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS.
 FOR OUT DOOR AIR AND EXHAUST 2010 FBC (M) .
 3) ADDRESS ON THE ENERGY CALCULATION AND PLANS DO NOT
 MATCH.
 4) PROVIDE PRODUCT APPROVALS FOR THE FRESH AIR AND
 EXHAUST
 OUTSIDE LOUVERS.