| 2013-02-01 15:22:32 | MECHANICAL PLANS DENIED | | | 1) NOTE 21 ON PAGE M1.2 REQUEST THAT YOU PAINT EXPOSED | | | DUCT. | | | FIBERGLASS, FLEX OR DUCT WRAP CAN NOT BE PAINTED. | | | PER SECTION 603.5 NONMETALLIC DUCT. AND THE MANUFACTURE | | | OF THE DUCT . | | | 2) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS. | | | FOR OUT DOOR AIR AND EXHAUST 2010 FBC (M) . | | | 3) ADDRESS ON THE ENERGY CALCULATION AND PLANS DO NOT | | | MATCH. | | | 4) PROVIDE PRODUCT APPROVALS FOR THE FRESH AIR AND | | | EXHAUST | | | OUTSIDE LOUVERS. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] | | | |
|