| 2013-02-02 19:27:49 | 550 SOUTH ROSEMARY AVENUE - SUITE #158 |
| | PERMIT #13010847 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| | SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR |
| | AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL |
| | HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS |
| | PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL |
| | BE PROVIDED. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE |
| | REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE |
| | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN |
| | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. SECTION |
| | 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES |
| | SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE |
| | DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE |
| | SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE SECTION |
| | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS |
| | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER |
| | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE |
| | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR |
| | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN |
| | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT |
| | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION |
| | SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |
| | SHEET A1.1: PROVIDE FLOOR PAINT OR BARRIER AT OUTSIDE |
| | PATIO INDICATING THAT THIS IS A DESIGNATED EXIT PATH |
| | FROM INTERIOR EXIT DOOR #8 TO THE EXTERIOR GATE. |
| | |