 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL RISER PLAN WHICH INCLUDES PANEL
 ?HV?. INDICATE THE SIZE OF THE PAD MOUNTED TRANSFORMER.
 PROVIDE A SYSTEM GROUNDING AND BONDING CONDUCTOR FOR
 THE TRANSFORMER. NEC 215.5
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION 505.3
  
 PROVIDE SAFE WORKING CLEARANCES AND DEDICATED WORKING
 SPACE AT ALL ELECTRICAL PANEL BOARDS AND TRANSFORMERS.
 INDICATE LOCATION OF TRANSFORMERS. PROVIDE A STRUCTURAL
 SUPPORT DETAIL FOR WALL OR CEILING MOUNTED
 TRANSFORMERS. NEC 110.26, 240.24
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST
 BE GFCI PROTECTED. NEC 210.8
  
 INDICATE THE REQUIRED SAFE CLEARANCES TO THE CEILING
 FANS. NEC 110.3
  
 PROVIDE A STRUCTURAL DETAIL FOR SUPPORT OF THE HANGING
 TELEVISIONS. FBC 1604.1
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA,
 CABLE, POS, AND FIRE ALARM SYSTEMS.
  
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  