| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | PROVIDE AN ELECTRICAL RISER PLAN WHICH INCLUDES PANEL |
| | ?HV?. INDICATE THE SIZE OF THE PAD MOUNTED TRANSFORMER. |
| | PROVIDE A SYSTEM GROUNDING AND BONDING CONDUCTOR FOR |
| | THE TRANSFORMER. NEC 215.5 |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. |
| | NEC 110.22, 110.16, 110.22 |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE |
| | WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC |
| | ENERGY CONSERVATION 505.3 |
| | |
| | PROVIDE SAFE WORKING CLEARANCES AND DEDICATED WORKING |
| | SPACE AT ALL ELECTRICAL PANEL BOARDS AND TRANSFORMERS. |
| | INDICATE LOCATION OF TRANSFORMERS. PROVIDE A STRUCTURAL |
| | SUPPORT DETAIL FOR WALL OR CEILING MOUNTED |
| | TRANSFORMERS. NEC 110.26, 240.24 |
| | |
| | ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST |
| | BE GFCI PROTECTED. NEC 210.8 |
| | |
| | INDICATE THE REQUIRED SAFE CLEARANCES TO THE CEILING |
| | FANS. NEC 110.3 |
| | |
| | PROVIDE A STRUCTURAL DETAIL FOR SUPPORT OF THE HANGING |
| | TELEVISIONS. FBC 1604.1 |
| | |
| | NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA, |
| | CABLE, POS, AND FIRE ALARM SYSTEMS. |
| | |
| | |
| | |