2013-02-07 16:34:45BUILDING PLAN REVIEW
 PERMIT: 13010847
 ADD: 550 S ROSEMARY # 158
 CONT: GREATER BAY INC
 TEL: (813)267-7391
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 FEB. 07/2013
 ACTION: DENIED
  
 1) PLEASE CORRECT THE ADDRESS ON THE PLANS TO 550 S
 ROSEMARY # 158 ON BOTH THE PLANS AND ENERGY
 CALCULATIONS.
  
 2) PLEASE CORRECT THE MINIMUM TYPE CONSTRUCTION, THIS
 BUILDING WAS BUILT UNDER THE 1994 SSBC CODE AS A TYPE
 II UNDER THE 2010 FBCTHE COMPARISON IS A TYPE I-B.
 PLEASE CORRECT ALL SHEETS THAT INDICATE THE 1994 SSBC
 TYPE II.
  
 3) SHEET A0.1 WINDICATES THE WIND DESIGN AS A 170 MPH
 ZONE BUT DOES NOT PROVIDE THE EXPOSURE TYPE NOR DOES
 THE PLANS PROVIDE PRESSURES POSITIVE/ NEGATIVE.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP.
  
 5) THE FLORIDA PRODUCT APPROVAL SUBMITTED FL 13407.R2
 SHEET 2 OF 10 PROVIDES TWO DESIN PRESSURES, ONE THAT IS
 FLUSH WITH SILL AND THE OTHER IS NOT, WHICH UNIT IS TO
 BE INSTALLED, THE PRESSURES ARE DIFFERENT. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) THE DOOR SCHEDULE IS FOUND ON A.01 DOOR # 6 IS A
 FIRE RATED DOOR THAT LEADS INTO A EXIT PASSAGE WAY, NO
 FIRE RATING HAS BEEN PROVIDED. 2010 FBC-B TABLE 715.4.
  
 7) SHEET A.02 PROVIDES DETAILS FOR FIRE RATED WALLS,
 BUT THE DETAILS DO NOT PROVIDE THE REQUIRED FIRE RATING
 FOR THE STRUCTURAL COLUMNS SEE 2010 FBC-B TABLE 601
 PRIMARY FRAMING MEMBERS 2 HR FOR TYPE IB.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved