| Date |
Text |
| 2013-02-12 13:13:55 | 3401 PARKER AVENUE - EQUIPMENT STORAGE BUILDING |
| | PERMIT #13010796 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. |
| | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE |
| | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 |
| | OF NFPA 101 FLORIDA EDITION 2009. THE PLANS INDICATE A |
| | FIRE-RATED PARTITION BETWEEN THE STORAGE OCCUPANCY AND |
| | BUSINESS OCCUPANCY. IF THIS WALL IS DESIGNED FOR |
| | OCCUPANCY SEPARATION, THE WALL SHOULD BE CONSTRUCTED AS |
| | A FIRE BARRIER WITH DOOR OPENINGS TO BE FIRE RATED FOR |
| | AT LEAST 45-MINUTES IN LIEU OF THE 20 MINUTE FIRE RATED |
| | DOORS SHOWN ON THE PLANS. |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| | CONTRAST THE BACKGROUND. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |