| Plan Review Notes For Permit 13010762 |
| Permit Number |
13010762 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-07 19:15:11 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED | | | IMPROVEMENT, FBC 107.2.1. DETAIL SHOULD INCLUDE THE | | | NAME AND SIGNATURE OF THE PERSON TAKING RESPONSIBILITY | | | FOR THE DESIGN, FS471,481, 489 AND ALSO INCLUDE THE | | | WIND DESIGN CRITERIA FBC RESIDENTIAL 301.2.1.1. WIND | | | DESIGN CRITERIA SHOULD BE A MINIMUM OF 170 MPH EXPOSURE | | | C (PLEASE INCLUDE ON PLAN). | | | | | | REVISE DETAIL TO INCLUDE STEEL REINFORCEMENT (SIZE, | | | MINIMUM EMBEDMENT, SPACING). | | | | | | 2. REVISE SITE PLAN TO CLEARLY SHOW LOCATION OF | | | PROPOSED IMPROVEMENTS, FBC 107.2.1. THE ARROW IS NOT | | | CLEAR AS TO WHETHER THIS IS IN THE FRONT OR SIDE. ALSO | | | INCLUDE A ROOM DESIGNATION FOR THE AREA AFFECTED BY | | | THIS CHANGE. IF THIS IS A BEDROOM, SHOW ALTERNATIVE | | | MEANS OF ESCAPE AND RESCUE FBC R 310. | | | | | | | | | | | | |
|