| 2013-02-22 14:46:33 | 13010720 | | | 700 S. ROSEMARY AVE #104 | | | L.A. FITNESS | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. | | | NEC 110.22, 110.16, 110.22 | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLANS SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | | | PROVIDE AND ILLUSTRATE THE SAFE WORKING CLEARANCES AND | | | DEDICATED WORKING SPACE AT ALL ELECTRICAL PANEL BOARDS | | | AND TRANSFORMERS. NEC 110.26, 240.24 | | | | | | PANEL DSA REQUIRES A MAIN BREAKER. NEC 408.36 | | | | | | OVERCURRENT PROTECTION OF TRANSFORMER T-DSA IS LIMITED | | | TO 125% OF ITS CURRENT RATING. NEC TABLE 450.3(B) | | | | | | INDICATE THE REQUIRED SAFE CLEARANCES TO THE CEILING | | | FANS. NEC 110.3 | | | | | | NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA, | | | CABLE TV, POS, AND FIRE ALARM SYSTEMS. | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|