| 2013-02-06 09:59:30 | BUILDING PLAN REVIEW |
| | PERMIT: 13010720 |
| | ADD: 700 S ROSEMARY # 104 |
| | CONT: TBD |
| | CONTACT: JORGE BENAVIDES |
| | TEL: (561)632-1900 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-0.0 & A-2.2 BOTH INDICATE THIS TO BE A TYPE |
| | II BUILDING, UNDER THE 1997 SBC THIS WOULD HAVE BEEN |
| | CORRECT, IN THE 2004 FBC TYPE VI BUILDINGS WERE |
| | ELIMINATED AND A RECLASSIFICATION TOOK PLACE, THIS |
| | BUILDING IS CURRENTLY CLASSIFIED UNDER THE 2010 FBC-B |
| | AS A BUILDING TYPE IB. PLEASE CORRECT ALL SHEETS. |
| | FIGURE 600 CONSTRUCTION TYPE COMPARISION 2007 FBC-B |
| | COMMENTARY. PLEASE UPDATE. |
| | |
| | 2) NEITHER SHEET A-0.0 NOR A-2.2 INDICATE THAT THIS |
| | TENANT SPACE IS A CHANGE OF OCCUPANCY. BARNES & NOBLE |
| | OCCUPIED THIS SPACE A MERCANTILE OCCUPANCY. LA FITNESS |
| | IS PROPOSING TO BECOME THE NEW TENANT, A A-3 OCCUPANCY. |
| | THE DESIGNER OF RECORD WILL NEED TO REVIEW THE 2010 |
| | EXISTING BUILDING CODE 901.3.1 FOR BUILDINGS THAT ARE |
| | UNDER GOING A PARTIAL CHANGE OF OCCUPANCY, SECTION 912 |
| | WILL APPLY. |
| | |
| | 2A) THE DESIGNER OF RECORD SHALL ELECT TO DESSIGN THIS |
| | TENANT SPACE UNDER EITHER SECTION: |
| | 912.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT |
| | SEPARATION. |
| | 912.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH |
| | SEPARATION. |
| | 2B) WHEN THE CONTRACTOR APPLIES FOR THE BUILDING |
| | PERMIT, UNDER THE HEADING, DESCRIPTION OF WORK, THE |
| | CONTRACTOR IS TO INCLUDE, "CHANGE OF OCCUPANCY". |
| | |
| | 3) SHEET A-0.0 & A-2.2 THE OCCUPANT LOAD COUNT IS NOT |
| | CORRECT, ROOM ID 200 THE AEROBICS ROOM IT APPEARS THE |
| | USEE OF 50 SQ FT PER PERSON IS WITH EQUIPMENT, THE |
| | CORRECT USEAGE SHOULD EITHER BE 15 NET OR 7 NET. FOR |
| | THE PURPOSE OF THIS REVIEW THE 15 SQ FT WILL BE USED |
| | FOR THE OCCUPANT LOAD COUNT. PLEASE CORRECT THE |
| | OCCUPANT LOAD AND REQUIRED EGRESS WIDTHS ON BOTH |
| | SHEETS. |
| | |
| | 4) 2010 EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR |
| | CHANGE TO HIGHER HAZARD CATEGORY. |
| | WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A |
| | HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE |
| | 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 4A) THE MONUMENTAL STAIR IS NOW AN ISSUE (A-3 |
| | OCCUPANCY) WHERE IT WAS NOT UNDER THE MERCANTILE |
| | OCCUPANCY. THE EXCEPTION FOR MONUMENTAL STAIRS IS FOUND |
| | UNDER 708.2 EXCEPTION # 7, THE MONUMENTAL STAIR NOT |
| | REQUIRED TO BE PART OF THE MEANS OF EGRESS BECAUSE |
| | THERE WERE 2 VERTICAL EXITS TO THE 2ND FLOOR. |
| | |
| | THE 2010 FBC-B SECTION 1028.2 REQUIRES 50 % OF THE |
| | TOTAL OCCUPANTS TO EXIT THROUGH THE MAIN EXIT. 1028.3 |
| | ASSEMBLY OTHER EXITS. EACH LEVEL OF AN ASSEMBLY |
| | OCCUPANCY SHALL HAVE ACCESS TO A MAIN EXIT AND SHALL BE |
| | PROVIDED WITH ADDITIONAL EXITS OF SUFFICIENT WIDTH TO |
| | ACCOMMODATE ONE-HALF OF THE TOTAL OCCUPANT LOAD SERVED |
| | BY THAT LEVEL. SUCH ADDITIONAL EXITS SHALL BE LOCATED |
| | AS FAR FROM THE MAIN ENTRANCE/EXIT AS PRACTICABLE. SUCH |
| | EXITS SHALL BE ACCESSIBLE FROM A CROSS AISLE OR A SIDE |
| | AISLE. PLEASE PROVIDE CODE COMPLIANCE. |
| | |
| | ANOTHER ISSUE THAT IS BORDER LINE IS THE OCCUPANT LOAD |
| | ON THE SECOND FLOOR AND A THIRD REQUIRED STAIRWAY 2010 |
| | FBC-B TABLE 1021.1 IF 501 OCCUPANTS ARE LOCATED ON THE |
| | 2ND FLOOR THEN A THIRD REQUIRED EXIT STAIR WILL ALSO BE |
| | REQUIRED. |
| | |
| | 5) THE PLANS DO NOT PROVIDE A SECTION THROUGH THE |
| | MONUMENTAL STAIRWAY, PLEASE PROVIDE SUCH SECTION |
| | PROVIDING DETAILS SUCH AS DRAFT CURTAIN AND SPRINKLER |
| | LOCATION. |
| | 2010 FBC-B 708.2 EXCEPTION 2.1. WHERE THE AREA OF THE |
| | FLOOR OPENING BETWEEN STORIES DOES NOT EXCEED TWICE THE |
| | HORIZONTAL PROJECTED AREA OF THE ESCALATOR OR STAIRWAY |
| | AND THE OPENING IS PROTECTED BY A DRAFT CURTAIN AND |
| | CLOSELY SPACED SPRINKLERS IN ACCORDANCE WITH NFPA 13. |
| | IN OTHER THAN GROUPS B AND M, THIS APPLICATION IS |
| | LIMITED TO OPENINGS THAT DO NOT CONNECT MORE THAN FOUR |
| | STORIES. PLEASE NOTE THIS EXCEPTION IS ONLY FOR |
| | BUSINESS & MERCANTILE, NOT FOR AN ASSEMBLY USE, PLEASE |
| | PROVIDE HOW THIS CODE VIOLATION WILL BE COMPLIED. |
| | |
| | 6) THE LIFE SAFETY PLANS HAVE SERIOUS PROBLEMS SINCE |
| | THE MONUMETAL STAIRS CAN NOT BE USED FOR EXITING AND |
| | SINCE THE 2ND FLOOR OCCUPANT LOAD IS AT 500 OCCUPANTS, |
| | NEITHER THE STAIRS NOR THE DOORS AT THE BACK OF THE |
| | BUILDING WILL HANDLE THESE OCCUPANT LOADS. THE DESIGNER |
| | IS TAKING A 36 INCH DOOR AND STATING 180 OCCUPANTS CAN |
| | EXIT THIS OPENING, WHEREAS THE CLEAR OPENING IS CLOSER |
| | TO 34 INCHES AND ONLY 170 OCCUPANTS CAN EXIT. FOR A |
| | PAIR OF DOUBLE DOORS 340 OCCUPANTS. THE BACK OF HOUSE |
| | SEERVICE CORRIDOR IS ALSO CONSIDERED A EXIT PASSAGEWAY |
| | SINCE IT IS A CONTINUATION OF THE VERTICAL EXIT. MANY |
| | OF THE DOORS IN THIS EXIT PASSAGEWAY DOORWAYS ARE NOT |
| | WIDE ENOUGH FOR THE NEW ASSEMBLY OCCUPANCIES THAT NOW |
| | EXIST. FOR EXAMPLE TO THE SOUTH THE SPACE WAS |
| | ORIGINALLY DESIGN FOR MERCANTILE OCCUPANCY, THIS IS NOW |
| | GOING TO BE A RESTRAUNT WITH DOUBLE THE OCCUPANT LOAD |
| | OF HOW THE EXIT PASSAGE WAY WAS DESIGNED. THE SAME HOLD |
| | TRUE JUST TO THE NORTH, A SECOND FLOOR NIGHTCLUB AND |
| | THE SECONDARY EXIT THAT LEADS TO THE EXIT STAIRS. |
| | PLEASE PROVIDE THE OCCUPANT LOADS THAT WILL SHARE THE |
| | EXITING FOR THIS COMMON EXIT PASSAGE WAY. PLEASE NOTE |
| | PART OF THE EXIT DISCHARGE A 4 FOOT WIDE SIDEWALK |
| | AND STAIRS., THE STAIRS WILL ONLY ALLOW FOR 160 |
| | OCCUPANTS. PLEASE PROVIDE THE LIFE SAFETY PLANS TO THE |
| | PUBLIC WAY. |
| | |
| | 7-9) COMPLIED. |
| | 10) STRUCTURAL WORK COMMENT # 10 TO BE COMPLETED UNDER |
| | THE LANDLORD PERMIT# 13030406. |
| | |
| | 11) PLANS ARE REQUIRED TO HAVE CITY PLACE APPROVAL WITH |
| | THEIR STAMP. |
| | |
| | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |