| Plan Review Notes For Permit 13010710 |
| Permit Number |
13010710 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-05 11:22:07 | 435 SOUTHERN BOULEVARD | | | PERMIT #13010710 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE PLANS INDICATE A 6'X6' AREA DESIGNATED AS "EXISTING | | | RELOCATED DUST COLLECTION SYSTEM". INDICATE WHAT THE | | | 15'X6' ADJACENT AREA REPRESENTS. | | | | | | THE PLANS DO NOT SHOWN ANY MECHANICAL EXHAUST OR DUST | | | COLLECTION DUCTWORK PENETRATING THE EXTERIOR WALL AND | | | ROUTING TO THE NEW ENCLOSURE. | | | | | | AN AUTOMATIC SPRINKLER SYSTEM IS REQUIRED TO PROTECT | | | WOODWORKING FACILITIES OF 2,500 SQ.FT. OR MORE. THIS | | | NEW ENCLOSURE WILL NEED TO BE PROTECTED WITH FIRE | | | SPRINKLERS AS WELL. | | | | | | THE "EXISTING" DUST COLLECTION SYSTEM APPEARS TO HAVE | | | BEEN INSTALLED WITHOUT PLANS OR PERMITS. A VOIDED | | | PERMIT (#09010050) TO ADD A DUST COLLECTION SYSTEM WAS | | | DISCOVERED IN 2009. PLAN REVIEW COMMENTS INDICATE A | | | CHANGE IN USE AT THIS LOCATION FROM CABINET SALES TO | | | CABINET MANUFACTURING. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|