| 2013-02-13 13:53:04 | BUILDING PLAN REVIEW |
| | PERMIT: 13010710 |
| | ADD: 435 SOUTHERN BLVD |
| | CONT: BAYSHORE OF SOUTH FLORIDA |
| | TEL: (561)691-9508 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | FEB.13/2013 |
| | ACTION: DENIED |
| | |
| | 1) A VOID PERMIT 09010050 FOR A DUST COLLECTION SYSTEM |
| | WAS NEVER ISSUED. THIS WORK WAS COMPLETED WITHOUT |
| | PREMIT AND WILL BE INCLUDED IN THIS REVIEW AS WELL AS A |
| | REQUIRED CHANGE OF OCCUPANCY. THE BUSINESS TAX LICENSE |
| | FOR THIS LOCATION IS FOR CABINET SALES A MERCANTILE AND |
| | STORAGE OCCUPANCY. THE MERCANTILE PORTION OF THE |
| | BUILDING HAS NOT CHANGED THE OCCUPANCY, BUT THE CABINET |
| | SHOP HAS CHANGED THE USE TO A F1 OCCUPANCY FBC-B 306.2, |
| | DEPENDING ON THE SQUARE FOOTAGE OF THE SHOP A, H2 |
| | OCCUPANCY. |
| | PLEASE PROVIDE A SCALED FLOOR PLAN OF THE BUILDING |
| | INDICATING THE RETAIL OR MERCANTILE PORTION OF THE |
| | BUILDING, STORAGE AREA AND THE F1 OR MANUFACTURING OF |
| | CABENTRY. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | 2) 2010 FBC-EXISTING BUILDING 901.3 CHANGE OF OCCUPANCY |
| | CLASSIFICATION. |
| | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| | CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912 |
| | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| | CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| | OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| | GROUP. |
| | |
| | 2A) EXST BLDG CODE 902.1 COMPLIANCE WITH THE BUILDING |
| | CODE. |
| | WHERE THE CHARACTER OR USE OF AN EXISTING BUILDING OR |
| | PART OF AN EXISTING BUILDING IS CHANGED TO ONE OF THE |
| | FOLLOWING SPECIAL OCCUPANCY CATEGORIES AS DEFINED IN |
| | THE FLORIDA BUILDING CODE, BUILDING, THE BUILDING SHALL |
| | COMPLY WITH ALL OF THE APPLICABLE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING: |
| | 8. INCIDENTAL USE AREAS. |
| | 9. HAZARDOUS MATERIALS. |
| | |
| | 2B) EXST BLDG COIDE SECTION 904 FIRE PROTECTION 904.1 |
| | GENERAL. FIRE PROTECTION REQUIREMENTS OF SECTION 912 |
| | SHALL APPLY WHERE A BUILDING OR PORTIONS THEREOF |
| | UNDERGO A CHANGE OF OCCUPANCY CLASSIFICATION. |
| | 912.2 FIRE PROTECTION SYSTEMS. |
| | FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTIONS 912.2.1 AND 912.2.2. |
| | |
| | 912.2.1 FIRE SPRINKLER SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. |
| | |
| | 912.2.2 FIRE ALARM AND DETECTION SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION |
| | APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT |
| | THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A |
| | FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED. |
| | |
| | 2010 FBC-B F] 903.2.4.1 WOODWORKING OPERATIONS. |
| | AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED |
| | THROUGHOUT ALL GROUP F-1 OCCUPANCY FIRE AREAS THAT |
| | CONTAIN WOODWORKING OPERATIONS IN EXCESS OF 2,500 |
| | SQUARE FEET (232 M2) IN AREA WHICH GENERATE FINELY |
| | DIVIDED COMBUSTIBLE WASTE OR USE FINELY DIVIDED |
| | COMBUSTIBLE MATERIALS. |
| | |
| | 3) 2010 FBC-B [F] 415.6 GROUP H-2. OCCUPANCIES IN GROUP |
| | H-2 SHALL BE CONSTRUCTED IN ACCORDANCE WITH SECTIONS |
| | 415.6.1 THROUGH 415.6.4 AND THE FLORIDA FIRE PREVENTION |
| | CODE.. |
| | [F] 415.6.1 COMBUSTIBLE DUSTS, GRAIN PROCESSING AND |
| | STORAGE. |
| | THE PROVISIONS OF SECTIONS 415.6.1.1 THROUGH 415.6.1.6 |
| | SHALL APPLY TO BUILDINGS IN WHICH MATERIALS THAT |
| | PRODUCE COMBUSTIBLE DUSTS ARE STORED OR HANDLED. |
| | BUILDINGS THAT STORE OR HANDLE COMBUSTIBLE DUSTS SHALL |
| | COMPLY WITH THE APPLICABLE PROVISIONS OF NFPA 61, NFPA |
| | 85, NFPA 120, NFPA 484, NFPA 654, NFPA 655 AND NFPA |
| | 664, AND THE FLORIDA FIRE PREVENTION CODE.. |
| | F] 415.6.1.1 TYPE OF CONSTRUCTION AND HEIGHT |
| | EXCEPTIONS. |
| | BUILDINGS SHALL BE CONSTRUCTED IN COMPLIANCE WITH THE |
| | HEIGHT AND AREA LIMITATIONS OF TABLE 503 FOR GROUP H-2; |
| | EXCEPT THAT WHERE ERECTED OF TYPE I OR II CONSTRUCTION, |
| | THE HEIGHTS AND AREAS OF GRAIN ELEVATORS AND SIMILAR |
| | STRUCTURES SHALL BE UNLIMITED, AND WHERE OF TYPE IV |
| | CONSTRUCTION, THE MAXIMUM HEIGHT SHALL BE 65 FEET (19 |
| | 812 MM) AND EXCEPT FURTHER THAT, IN ISOLATED AREAS, THE |
| | MAXIMUM HEIGHT OF TYPE IV STRUCTURES SHALL BE INCREASED |
| | TO 85 FEET (25 908 MM) |
| | SUBMIT PLANS FOR THE DUST COLLECTION SYSTEM THAT WAS |
| | ALREADY INSTALLED BUT NEVER PERMITED. |
| | |
| | 4) THE PERMIT DESCRIPTION AND VALUE WILL NEED TO BE |
| | UPDATED TO REFLECT BOTH THE UNPERMITED WORK AND THE |
| | PROPOSED NEW WORK. |
| | |
| | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |