| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| | SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR |
| | AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL |
| | HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS |
| | PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL |
| | BE PROVIDED. |
| | |
| | THE NORTH HALF OF THE BUILDING SHOWING THE STORAGE AREA |
| | AND PERSONAL TRAINING ROOM WAS NOT SUBMITTED IN THE |
| | ARCHITECTURAL DRAWINGS. |
| | |
| | IN BUILDINGS NOT PROTECTED BY A SPRINKLER SYSTEM, THE |
| | MINIMUM SEPARATION DISTANCE BETWEEN TWO EXITS OR EXIT |
| | ACCESS DOORS SHALL BE NOT LESS THAN ONE-HALF THE LENGTH |
| | OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE |
| | BUILDING OR AREA BEING SERVED. |
| | |
| | PLANS DO NOT INDICATE ANY FIRE-RATED WALLS SEPARATING |
| | THE ASSEMBLY OCCUPANCIES FROM THE STORAGE OCCUPANCY. |
| | EACH NEW FIRE-RATED BARRIER SHALL BE PERMANENTLY |
| | IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE |
| | BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT |
| | LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| | CENTER. PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY |
| | SHALL BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| | |
| | PROVIDE A FURNITURE AND EQUIPMENT LAYOUT PLAN. |
| | |
| | NO FLAME SPREAD OR SMOKE DEVELOPMENT INFORMATION |
| | PROVIDED FOR INTERIOR WALL AND CEILING FINISH |
| | MATERIALS. |
| | |
| | PROVIDE A BREAKDOWN SHOWING THE ROOM SQUARE FOOTAGE |
| | AREAS AND THE OCCUPANT LOAD FACTORS USED FOR DETERMING |
| | OCCUPANT LOAD. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | PERSONAL TRAINING ROOM SHALL NOT EXIT THROUGH A MORE |
| | HAZARDOUS ROOM (STORAGE). |
| | |
| | NO DOOR SCHEDULE OR HARDWARE INFORMATION PROVIDED. FOR |
| | ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR |
| | MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS |
| | TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES |
| | ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC |
| | HARDWARE. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | ELECTRICAL DRAWINGS DO NOT SHOW ANY CIRCUITRY SUPPLYING |
| | THE EXIT SIGNS. |
| | |
| | EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM |
| | OF 1? HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING. |
| | EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO |
| | PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN |
| | AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN |
| | 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT |
| | FLOOR LEVEL. |
| | |
| | AT THIS TIME A THOROUGH AND COMPLETE PLAN REVIEW CANNOT |
| | BE PERFORMED DUE TO LACK OF PLAN INFORMATION. |
| | |