| 2013-01-30 16:15:30 | BUILDING PLAN REVIEW |
| | PERMIT: 13010708 |
| | ADD: 4115 GEORGIA AVE |
| | CONT: BAYSHORE OF SOUTH FLORIDA |
| | TEL: (561)691-9508 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1: |
| | |
| | 1A) BUILDING DATA UNDER THE HEADING OCCUPANCY GROUP IS |
| | LISTED AS A A-3 OCCUPANCY AND THE OCCUPANCY LOAD IS |
| | INDICATED AS 50 GROSS /W EQUIPMENT. NEITHER SHEET A1 |
| | NOR A2 SHOW THE EQUIPMENT LAYOUT, NOR DOES THE PLAN |
| | INDICATE WHICH AREAS OF THE BUILDING WILL MAKE UP THE |
| | 5846 SQ FT OF THE GYM. 2010 FBC TABLE 1004.1.1. THE |
| | PLANS AS NOT HAVING EQUIPMENT SHOWN WE SHOULD USE 15 SQ |
| | FT /OCCUPANT WHICH WILL PRODUCE A OCCUPANT LOAD OF 389. |
| | |
| | 1B) THE BUILDING DATA FOUND ON THIS PAGE DECLARES THIS |
| | BUILDING TO BE A BUILDING TYPE 2A WHERE AS ON THE LIFE |
| | SAFETY SHEET THE BUILDING IS DECLARED AS A TYPE IIB |
| | (UNPROTECTED). DISCREPANCY, ADDITIONAL INFORMATION IS |
| | REQUIRED, 107.2.1.3. |
| | |
| | |
| | 1C) SHEET A1. PLEASE PROVIDE THE ACCESSIBLE PATH FROM |
| | ACCESSIBLE PARKING SPACE # 17 TO THE ENTRANCE. 2010 |
| | ACCESSIBILITY CODE 202.4 ALTERATIONS AFFECTING THE |
| | PRIMARY FUNCTION AREAS. PLEASE ALSO REVIEW 202.4.1 |
| | DISPROPORTIONATE COST & 202.4.2 ACCESSIBLE FEATURES IN |
| | THE EVENT OF DISPROPORTIONALITY. |
| | |
| | 2) SHEET A2 IS NOT SHOWING THE TOTAL TENANT SPACE, |
| | THERE IS APPROXIMATELY ANOTHER 80 LINIER FEET OF |
| | BUILDING NOT SHOWN. IT IS NOT CLEAR WHERE THE TENANT |
| | SEPERATION WALL WILL OCCUR OR IF THE PERSONNAL TRAINING |
| | ROOM IS PART OF THIS PROJECT, AGAIN WHAT OR HOW WILL |
| | THE OCCUPANT LOAD FOR THIS ARE ROOM BE CALCULATED. 2010 |
| | FBC TABLE 1004.1.1. |
| | |
| | 3) ON SHEET A2 THERE APPEARS TO BE A DISCREPANCY |
| | BETWEEN WHAT IS THERE NOW AND WHAT WAS SHOWN ON THE |
| | LAST KNOWN PERMIT WITH ELEVATIONS OF THE EAST WALL. |
| | PERMIT # 12050428 FOR NEW FRONT DOUBLE DOORS INDICATED |
| | ON THE LONG NARROW PORTION OF THE BUILDING FACING EAST |
| | 3 LARGE OVER HEAD DOORS AND JALOUSE WINDOWS, ON SHEET |
| | A2 SLIDDING DOOR ARE SHOWN AND NO WINDOWS. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | NOTE: 2010 EXST BLDG CODE 901.3 CHANGE OF OCCUPANCY |
| | CLASSIFICATION. |
| | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| | CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912 |
| | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| | CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| | OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| | GROUP. |
| | |
| | 4) 2010 EXST BLDG CODE 912.2 FIRE PROTECTION SYSTEMS. |
| | FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTIONS 912.2.1 AND 912.2.2. |
| | 912.2.1 FIRE SPRINKLER SYSTEM. |
| | |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. |
| | |
| | 2010 FBC-B F] 903.2.1.3 GROUP A-3. AN AUTOMATIC |
| | SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-3 |
| | OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS |
| | EXISTS: |
| | (2). THE FIRE AREA HAS AN OCCUPANT LOAD OF 300 OR MORE. |
| | |
| | 5) 2010 EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION |
| | SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION |
| | OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM |
| | TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE |
| | WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, |
| | SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE |
| | THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM |
| | NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY |
| | ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING |
| | IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM |
| | NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT |
| | THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL |
| | BE AUTOMATICALLY ACTIVATED. |
| | |
| | 2010 FBC-B [F] 907.2.1 GROUP A. |
| | A MANUAL FIRE ALARM SYSTEM THAT ACTIVATES THE OCCUPANT |
| | NOTIFICATION SYSTEM IN ACCORDANCE WITH SECTION 907.5 |
| | SHALL BE INSTALLED IN GROUP A OCCUPANCIES HAVING AN |
| | OCCUPANT LOAD OF 300 OR MORE. EXCEPTION: MANUAL FIRE |
| | ALARM BOXES ARE NOT REQUIRED WHERE THE BUILDING IS |
| | EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM |
| | INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 AND THE |
| | OCCUPANT NOTIFICATION APPLIANCES WILL ACTIVATE |
| | THROUGHOUT THE NOTIFICATION ZONES UPON SPRINKLER |
| | WATERFLOW. |
| | |
| | 6) 2010 EXST BLDG CODE 912.3 INTERIOR FINISH. IN AREAS |
| | OF THE BUILDING UNDERGOING THE CHANGE OF OCCUPANCY |
| | CLASSIFICATION, THE INTERIOR FINISH OF WALLS AND |
| | CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING FOR THE NEW OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | 7) 2010 EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR |
| | CHANGE TO HIGHER HAZARD CATEGORY. |
| | WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A |
| | HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE |
| | 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | THE MAIN WORK OUT AREA SHOWN ON SHEET A2 & LS1 HAS TWO |
| | EXIT DOORS LEADING TO THE EXTERIOR THERE IS A 3RD DOOR |
| | THAT LEADS INTO A STORAGE AREA. THE TWO DOUBLE DOORS |
| | THAT LEAD TO THE EXTERIOR ARE NOT 1/2 OF THE DIAGONAL |
| | DISTANCE FOR THAT ROOM, PLEASE SEE 2010 FBC-B 1015.2.1 |
| | TWO EXITS OR EXIT ACCESS DOORWAYS. |
| | WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE REQUIRED |
| | FROM ANY PORTION OF THE EXIT ACCESS, THE EXIT DOORS OR |
| | EXIT ACCESS DOORWAYS SHALL BE PLACED A DISTANCE APART |
| | EQUAL TO NOT LESS THAN ONE-HALF OF THE LENGTH OF THE |
| | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR |
| | AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN |
| | EXIT DOORS... |
| | |
| | PLEASE NOTE THE DOOR THAT LEADS TO THE STORAGE ROOM AND |
| | TO THE EXTERIOR CAN NOT BE USED AS AN EXIT. 2010 FBC-B |
| | 1014.2 EGRESS THROUGH INTERVENING SPACES. |
| | EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH |
| | THIS SECTION. (4.) EGRESS SHALL NOT PASS THROUGH |
| | KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED FOR |
| | SIMILAR PURPOSES. |
| | |
| | 8) PLANS DO NOT INDICATE THE TYPE OF HARDWARE FOR THE |
| | EXIT DOORS, NEITHER DOES THE CLOSED PERMIT 12050428 FOR |
| | THE FRONT DOORS. 2010 FBC-B 1008.1.10 PANIC AND FIRE |
| | EXIT HARDWARE. DOORS SERVING A GROUP H OCCUPANCY AND |
| | DOORS SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF |
| | 50 OR MORE IN A GROUP A OR E OCCUPANCY SHALL NOT BE |
| | PROVIDED WITH A LATCH OR LOCK UNLESS IT IS PANIC |
| | HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | 9) THE PLANS DO NOT PROVIDE THE TYPE OF FINISHES AND |
| | BASE MATERIALS TO BE INSTALLED IN THE RESTROOMS. |
| | 2010 FBC-B 1210.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF URINALS |
| | AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) |
| | ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, |
| | THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE |
| | THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 1210.3 SHOWERS. |
| | SHOWER COMPARTMENTS AND WALLS ABOVE BATHTUBS WITH |
| | INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A SMOOTH, |
| | NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 70 |
| | INCHES (1778 MM) ABOVE THE DRAIN INLET. |
| | |
| | 10) SHEET A3 DOES NOT INDICATE WHAT TYPE OF SHEATHING |
| | OR BASE WILL BE USED FOR THE SHOWER WALLS, PLEASE |
| | REVIEW SECTIONS BELOW, ALSO THE PLANS INDICATE THE USE |
| | OF PAINTED MR BOARD FOR THE CEILINGS BUT THE THICKNESS |
| | OF THE GYPSUM BOARD IS NOT PROVIDED NOR IS THE SPAN FOR |
| | THE CEILING FRAMING PROVIDED IN THE SHOWERS, PLEASE |
| | PROVIDE DOCUMENTATION FOR CODE COMPLIANCE. |
| | 2509.2 BASE FOR TILE. |
| | GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS, |
| | DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE |
| | SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT |
| | SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288 |
| | OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| | RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| | IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| | SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| | SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| | COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| | GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| | REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| | WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| | |
| | 2509.3 LIMITATIONS. |
| | WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED |
| | IN THE FOLLOWING LOCATIONS: |
| | |
| | 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| | COMPARTMENTS. |
| | |
| | 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| | AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| | |
| | 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| | (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| | INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD. |
| | |
| | 11) PLEASE REVIEW THE ADA-1 SHEET FOR THE ACCESSIBLE |
| | SHOWER COMPARTMENTS, IT IS NOT CLEAR IF THE DESIGNER IS |
| | TRYING TO COMPLY WITH THE 2010 ACCESSIBILITY CODE |
| | 608.2.2 FOR A STANDARD ROLL IN TYPE SHOWER OR 608.2.3 |
| | ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENT. IF YOU ARE |
| | DESIGNING TO STANDARD ROLL-IN TYPE SHOWER COMPARTMENT |
| | THEN THE PLANS ARE NOT IN COMPLIANCE WITH 608.2.2.1. |
| | |
| | IF DESIGNED TO THE ALTERNATE ROLL-IN TYPE SHOWER, THE |
| | DESIGNER WILL NEED TO REVIEW SECTIONS THAT DEAL WITH: |
| | 2010 ACCESSIBILITY CODE: |
| | 608.3.3 POSITIONING AND LENGTH OF BACKING ,AND REQUIRED |
| | GRAB BARS AND THE REQUIRED LENGHT OF GRAB BARS |
| | 608.4 SEAT LOCATION (OPTIONAL) |
| | 608.5 CONTROLS STANDARD ROLL IN VS TRANSFER TYPE |
| | SHOWER? |
| | 608.5.3 CONTROL LOCATIONS |
| | 608.6 SHOWER SPRAY UNIT AND WATER |
| | 608.7 THRESHOLDS |
| | |
| | 12) 12) PLEASE REVIEW ADA-1 SHEET THE ACCESSIBLE |
| | SHOWERS AND THE BENCHES AT THE ENTRANCE TO THE SHOWERS. |
| | THESE ACCESSIBLE BENCHES WILL BE REQUIRED TO MEET THE |
| | REQUIREMENTS FOUND UNDER TTHE 2010 FL ACCESSIBILTY CODE |
| | 903 1-7. |
| | |
| | 13) PLEASE PROVIDE THE DIMENSION FROM TTHE BUILDING TO |
| | THE WEST PROPERTY LINE WALL TO SHOW COMPLIANCE WITH |
| | 2010 EXST BLDG CODE 912.6 EXTERIOR WALL FIRE RATING, |
| | AND 912.6.1. |
| | |
| | 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |