| 2013-02-07 12:43:05 | FBC 2010 ACCESSIBILITY CODE |
| | FBC 2010 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | 1. A LAVATORY IS REQUIRED IN THE ACCESSIBLE RESTROOM |
| | STALLS. |
| | FBC ACCESSIBILITY 2010 604.8.1.6 LAVATORY. IN NEW |
| | CONSTRUCTION, THE WHEELCHAIR ACCESSIBLE TOILET |
| | COMPARTMENT SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN |
| | IT, WHICH MUST BE AT LEAST 19 INCHES WIDE BY 17 INCHES |
| | DEEP, NOMINAL SIZE, AND WALL-MOUNTED. THE LAVATORY |
| | SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR |
| | SPACE AREAS REQUIRED BY SECTION 604 FOR THE WHEELCHAIR |
| | ACCESSIBLE TOILET COMPARTMENT AND SHALL COMPLY WITH |
| | SECTION 606. SUCH LAVATORIES SHALL BE COUNTED AS PART |
| | OF THE REQUIRED FIXTURE COUNT FOR THE BUILDING. SEE |
| | ALSO SECTION 213.3.4. |
| | |
| | 2. SHEET P1.1 IF FPWH IS A WALL HYDRANT, THEY REQUIRE |
| | SEPARATE SHUT OFF VALVES. |
| | 606.2 LOCATION OF SHUTOFF VALVES. (2) ON THE WATER |
| | SUPPLY PIPE TO EACH SILLCOCK IN OTHER THAN ONE- AND |
| | TWO-FAMILY RESIDENTIAL OCCUPANCIES. |
| | |
| | 3. SHEET P2.1, P5.1 PLEASE SHOW THE KITCHEN MOP SINK |
| | CONNECTED TO THE GREASE SYSTEM. |
| | 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE |
| | REMOVAL DEVICES REQUIRED. |
| | A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE |
| | SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES |
| | AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD |
| | PREPARATION AREAS... |
| | |