| Notes |
| Date |
Text |
| 2013-02-08 13:17:53 | MECHANICAL PLANS DENIED | | | 1) PROVIDE HEAT & COOLING LOADS WITH THE PLANS | | | PER SECTION 503.2.1 FLORIDA ENERGY CODE 2010 | | | 2) REFER TO SECTION503.2.4.4 SHUT OFF DAMPER CONTROLS. | | | 2010 FLORIDA ENERGY CODE. | | | 3) PROVIDE DUCT SIZE ON ALL EXHAUST DUCT. | | | PER SECTION 107 FBC. | | | 4) PROVIDE A DETAIL ON THE RTU TO CURB TIE DOWN FROM | | | THE | | | ENGINEER. PER SECTION 301.12 WIND RESISTANCE 2010 FBC | | | (M) | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|