Plan Review Notes
Plan Review Notes For Permit 13010628
Permit Number 13010628
Review Stop G
Sequence Number 1
Notes
Date Text
2013-02-07 15:53:05FBC 2010 FUEL GAS REVIEW #1
 DENIED:
  
 SHEET MEP 1.1 , P5.1 SHOWS REGULATORS WITH A SHUTOFF
 VALVE DOWNSTREAM.
 409.4 MP REGULATOR VALVES.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR.
  