| Plan Review Notes For Permit 13010628 |
| Permit Number |
13010628 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-07 15:53:05 | FBC 2010 FUEL GAS REVIEW #1 | | | DENIED: | | | | | | SHEET MEP 1.1 , P5.1 SHOWS REGULATORS WITH A SHUTOFF | | | VALVE DOWNSTREAM. | | | 409.4 MP REGULATOR VALVES. | | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | | AHEAD OF EACH MP REGULATOR. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|