2013-02-04 14:10:502471 OKEECHOBEE BOULEVARD - #777
 PERMIT #13010628
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS.1: UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET D1.0: ALL CONSTRUCTION AND DEMOLITION WORK SHALL
 CONFORM TO THE REQUIREMENTS OF NFPA 241. SMOKING SHALL
 BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 SHEET D1.0: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 INDICATE THE FLAME SPREAD AND SMOKE DEVELOPEMENT
 CLASSIFICATION OF WALL AND CEILING FINISHES.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SHEET E1.1: PLANS APPEAR TO SHOW ONLY 6 EMERGENCY
 LIGHTING FIXTURES.
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE SPEAKER/STROBE NOTIFICATION APPLIANCES AS NEW
 ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING
 300 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY
 VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. REFERENCE
 SECTION 12.3.4.3.3 OF FLORIDA FIRE PREVENTION CODE ?
 NFPA 101
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM, FIRE ALARM SYSTEM, KITCHEN EXHAUST HOOD, AND
 KITCHEN HOOD FIRE SUPPRESSION SYSTEM.
  