 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION 505.3
  
 PROVIDE AND ILLUSTRATE THE SAFE WORKING CLEARANCES AND
 DEDICATED WORKING SPACE AT ALL ELECTRICAL PANEL BOARDS
 AND TRANSFORMERS. NEC 110.26, 240.24
  
 REVISE ELECTRICAL SERVICE RISER PLAN TO SHOW FEEDERS
 WITH 400 AMP CAPACITY. NEC 215.5, T310.16
  
 REVISE MDP SCHEDULE TO REFLECT THE APPROPRIATE OVER
 CURRENT PROTECTION FOR THE FEEDER TO THE ELECTRICAL
 PANELS. NEC 240.4, T. 310.16
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA,
 CABLE, POS, AND FIRE ALARM SYSTEMS.
  
  