| Plan Review Notes For Permit 13010628 |
| Permit Number |
13010628 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-14 08:53:16 | 13010628 | | | 2471 OKEECHOBEE BLVD | | | CHUCK E CHEESE | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. | | | NEC 110.22, 110.16, 110.22 | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE | | | WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC | | | ENERGY CONSERVATION 505.3 | | | | | | PROVIDE AND ILLUSTRATE THE SAFE WORKING CLEARANCES AND | | | DEDICATED WORKING SPACE AT ALL ELECTRICAL PANEL BOARDS | | | AND TRANSFORMERS. NEC 110.26, 240.24 | | | | | | REVISE ELECTRICAL SERVICE RISER PLAN TO SHOW FEEDERS | | | WITH 400 AMP CAPACITY. NEC 215.5, T310.16 | | | | | | REVISE MDP SCHEDULE TO REFLECT THE APPROPRIATE OVER | | | CURRENT PROTECTION FOR THE FEEDER TO THE ELECTRICAL | | | PANELS. NEC 240.4, T. 310.16 | | | | | | NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA, | | | CABLE, POS, AND FIRE ALARM SYSTEMS. | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|