Plan Review Notes
Plan Review Notes For Permit 13010628
Permit Number 13010628
Review Stop B
Sequence Number 1
Notes
Date Text
2013-02-08 10:15:07BUILDING PLAN REVIEW
 PERMIT: 13010628
 ADD: 2471 OKEECHOBEE BLVD
 CONT: TBD/ PARKWAY CONSTRUCTION
 TEL: (469)322-3758
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 FEB. 08/2013
 ACTION: DENIED
  
 1) THE ADDRESS PROVIDED ON THE PLANS AS WELL AS THE
 PERMIT APPLICATION IS THE SITE ADDRESS FOR THE WHOLE
 PARCEL. THIS TENANT EITHER HAS AN INDIVIDUAL STREET
 ADDRESS OR A SUITE NUMBER TO IDENTIFY THE INDIVIDUAL
 TENANT SPACE FOR INSPECTION PURPOSES, RECORDS, RECORD
 RETENSION AS WELL AS EMERGENCIES. 105.3 ACTION ON
 APPLICATION WPB AMENDMENTS TO ADMINISTRATIVE CODE,
 CHAPTER 1/ 2010 FBC.
  
 2) CHANGE OF OCCUPANCY FROM MERCANTILE TO A2 ASSEMBLY,
 ENERGY CALCULATIONS REQUIRED, 2010 FBC-ENERGY CODE 913.
  
 3) THESE PLANS APPEAR TO HAVE VARIOUS DETAILS THAT MAY
 NOT BE APPLICABLE TO THIS PERMIT. IF THE DETAILS DO NOT
 SERVE THIS PROJECT PLEASE EITHER DELETE THE DETAIL OF
 CROSS THEM OUT. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. WPB ADMINMENTS TO THE ADMINISTRTIVE CODE
 2010.
  
 4) SHEET A1.0 & A1.1 DETAIL # 3 INDICATES A STAGE.
 NOTES INDICATE THE STAGE TO BE BUILT BY OTHERS, WILL
 THE DESIGN OF THE STAGE BE PART OF THE DESIGNER OF
 RECORDS PERMIT SET OF DRAWINGS? IF IT IS NOT THEN IT
 SHOULD NOT BE IN THIS PACKAGE. THERE ARE TWO ISSUES AT
 HAND WITH THE STAGE;
 4A) NO PLANS INDICATING THE TYPE OF MATERIALS THE STAGE
 IS TO BE CREATED FROM, NOR IS THE HEIGTH OF THE STAGE
 PROVIDED? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
 4B) HOW VERTICAL ACCESSIBILITY WILL BE ADDRESSED. 2010
 FBC ACCESSIBILITY 201.1.1.
  
 5) SHEET A-0.1 & S-2.0 BOTH INDICATE A NEW DOORWAY AND
 ACCESSIBLE RAMP. PLEASE REVIEW TTHE 2010 ACCESSIBILITY
 CODE 405.7.4.RAMPS, CHANGE IN DIRECTION. THE PLAN DOES
 NOT INDICATE A BOTTOM LANDING, IS THERE ENOUGH ROOM?
 2010 ACCESSIBILITY 405.7.
  
 6) SHEET A-0.1 & A1.0 BOTH INDICATE THE NEW HANDRAIL
 BUT THE PLANS FAIL TO PROVIDE DETAILS FOR THE HANDRAIL
 PER 2010 ACCESSIBILITY CODE 405.8.
  
 7) SHEET A-3.1 & A-7.1:
 7A) THE PLANS INDICATE A NEW ROOF HATCH, FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:(31)(A) ACCESS
 HATCHES. PLEASE ALSO REVIEW GUARDS 1013.6.
  
 7B) A-7.1 & M1.3 BOTH INDICATE A DETAIL FOR RAISED
 CURBS, PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE NEW
 CURB THAT IS BEING INSTALLED FOR A/C UNIT #4. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
  
 7C) THE PLANS INDICATE THE EXISTING CURBS ARE TO HAVE
 AN ADAPTOR OVER THE EXISTING CURB, PLEASE PROVIDE THE
 MANUFACTURERS SPECIFICATIONS .HOW THEY WILL BE SECURED
 TO THE EXISTING CURB? 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 7D) A-7.1 DETAIL # 3 INDICATES THE USE OF WOOD SLEEPERS
 AND PITCH PANS, THIS HAS NOT BEEN ALLOWED IN FLORIDA
 SINCE THE 2001 FBC. 2010 FBC-B TABLE 1509.7 PROVIDES
 THE REQUIRED HEIGHT OF THE UNIT ABOVE THE ROOF COVERING
 DEPENDING ON THE WIDTH OF THE UNIT.
  
 7E) A/C STANDS FOR ROOF TOP CONDENSORS. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS: (31)((G)
 PRE-ENGINEERED A/C STANDS.
  
 7F) ROOF TOP BLOX, AN ENGINEERING LAB TEST REULTS WERE
 SUBMITTED IT APPEARS TO BE A SITE SPECIFIC CASE IN
 ELLINGTON, MAINE FOR A 150 MPH WIND ZONE. WE DO ACCESPT
 NATIONALLY RECONIZED REPORTS FROM THE ICC ER REPORTS,
 ERS REPORTS ETC, PLEASE PROVIDE A CURRENT REPORT FROM A
 NATIONALLY RECONIZED TESTING AGENCY.
  
 8) A ROOFING PERMIT WILL BE REQUIRED FOR ALL ROOF
 REPAIRS FOR THE NEW OPENINGS WITHIN THE ROOF AND CURBS
 THAT ARE BEING INSTALLED. FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES FLAT ROOF
 REPAIR AS WELL AS THE METAL FOR THE AWNING DETAIL.
  
 9) THE SHEET A-7.2 INDICATES THE USE OF EFIS WALL
 INSULATION AND WALL FINISHES, PLEASE PROVIDE THE
 PRODUCT APPROVAL FOR EFIS WALL SYSTEMS. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) , EFIS SYSTEMS,
  
 10) SHEET A-7.4 DETAIL # 13 BOOTHS BY OTHERS. PLEASE
 PROVIDE WHAT TYPE OF MATERIALS WILL BE USED IN COVERING
 THE BOOTHS. 2010 FBC-B 806.4.
  
 11) SHEET A-8.0 THE DOOR SCHEDULE ALL EXIT DOORS WILL
 REQUIRE PANIC HARDWARE IT APPEARS DOOR # 1 & 7 DO NOT
 INDICATE PANIC HARDWARE IN THE HARDWARE SCHEDULE. DOOR
 # 3 INDICATES EXISTING AND DOES NOT LIST ANY HARDWARE.
 2010 FBC-B 1008.1.10.
  
 12) SHEET A-9.2 PLEASE REVIEW THE MENS & WOMENS
 HANDICAPPED STALL REQUIREMENTS, 2010 FLORIDA
 ACCESSIBILITY CODE REQUIRES THE LAV TO BE IN THE SAME
 TOILET COMPARTMENT,
 SEE 604.8.1.6, 604.8.1.7
  
 13) SHEET A-9.2 INDICATE THE RESTROOMS TO HAVE A TILE
 FINISH ON THE WALLS BUT THE PLANS DO NOT PROVIDE WHAT
 TYPE OF BACKER BOARD IS TO BE INSTALLED. SEE:
 13A) 210.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
 13B) 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT
 SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288
 OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 14) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 14.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 14.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 14.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 14.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 14.5) COMPONENTS & CLADDING PRESSURES POSITVE &
 NEGATIVE TABLE 1609.2(2) . PROVIDE PRESSURES FOR ZONES
 1-5 ROOF & WALL ZONES.
  
 15) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  