Date Text
2013-02-11 10:35:3113010622
 5014 PINEWOOD AVE.
 RESIDENTIAL REPAIR
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 IF THE RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE
 OR A FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. 2010
 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 PROVIDE AN ELECTRIC SERVICE RISER SHOWING THE PANEL,
 MAIN BREAKER, CONDUIT AND FEEDERS. PROVIDE PANEL
 SCHEDULES EACH UNIT. NEC 215.15
  
 A SEPARATE PERMIT IS REQUIRED FOR EACH STRUCTURE.
  
  