| Plan Review Notes For Permit 13010622 |
| Permit Number |
13010622 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-11 10:35:31 | 13010622 | | | 5014 PINEWOOD AVE. | | | RESIDENTIAL REPAIR | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | IF THE RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE | | | OR A FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED | | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. 2010 | | | FBC R314, 315 | | | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | | | THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | | | | PROVIDE AN ELECTRIC SERVICE RISER SHOWING THE PANEL, | | | MAIN BREAKER, CONDUIT AND FEEDERS. PROVIDE PANEL | | | SCHEDULES EACH UNIT. NEC 215.15 | | | | | | A SEPARATE PERMIT IS REQUIRED FOR EACH STRUCTURE. | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|